2 module status – NORD Drivesystems BU0080 User Manual
Page 25

5 Frequency inverter settings
25
Parameter
Setting value / Description / Note
Comments
P745
... - 01
…
... - 03
Module version
SK 700E, SK 750E
0.0 ... 3276.7
Software version of the installed module
[01]
Technology
unit
(E.g.:
DeviceNet
Technology
Unit)
[02]
Customer
Unit
[03] Special Extension Unit
P746 Module
status
SK 300E, SK 500E
0000 ... FFFF (hex)
Indicates the actual status (readiness, error, communication) of the technology unit (SK TU2/3-
xxx), but only when own processor is present, therefore not for the SK TU2/3-CTR.
Code details can be found in the respective BUS module manual. Different contents are shown
depending on the modules. (DeviceNet: See Section 5.2 )
P746
... - 01
…
... - 03
Module status
SK 700E, SK 750E
0000 ... FFFF (hex)
Status of integrated modules
[01] Technology unit
(E.g.: DeviceNet Technology Unit)
[02]
Customer
Unit
[03] Special Extension Unit
NOTE
When activated, the functions block current, quick stop, remote control and cancel error
are available at the (local) control terminals. To operate the drive, a high signal must be present
on the digital inputs being used before the drive can be enabled.
5.2 Module status
In parameter P746, the status of the DeviceNet module can be read.
Parameter P746 is a subindex parameter: Subindex 0 contains the status of the DeviceNet technology unit.
The parameter contains binary coded information which is displayed in hexadecimals:
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Module ID
DeviceNet=0E
hex
Module ready
Module in status “operational”
E.g.: 0E03
hex
= DeviceNet module, module
ready and operational
Initialisation active
Reserved (0)
Module error
Timeout error
Initialisation error
Reserved (0)