Dwyer 32DZ User Manual

Page 31

background image

June, 2000

Page 31 of 40

949-1318

Note: If both Set Point 1 and Set Point 2 are set for temperature
inputs, they must both be set for the same scale. While it is possible
to set one input as degrees F and the other degrees C, since there
is only one descriptor, one of the displays is likely to be mis-read.
If one Set Point is set for process input, you may select to display
either the temperature descriptor or neither (nonE).

dPt2

dPt2

dPt2

dPt2

dPt2

Decimal Point Positioning: Select

0

00

00

,

0.0

0.0

0.0

0.0

0.0

,

0.00

0.00

0.00

0.00

0.00

, or

0.000

0.000

0.000

0.000

0.000

. On

temperature type inputs this will only effect the Process
Value, SP1, SP2, and InC1|InC2. For Current and Voltage
Inputs all Menu Items related to the Input will be affected.

0

00

00

No decimal Point is selected. This is available for
all Input Types.

0.0

0.0

0.0

0.0

0.0

One decimal place is available for Type J, K, E, T,
L, RTD’s, Current and Voltage Inputs.

0.00

0.00

0.00

0.00

0.00

Two decimal places is only available for Current
and Voltage Inputs.

0.000

0.000

0.000

0.000

0.000

Three decimal places is only available for Current

and Voltage inputs.

Int2

Int2

Int2

Int2

Int2

Input Fault Timer: Select

OFF

OFF

OFF

OFF

OFF

,

0.1

0.1

0.1

0.1

0.1

to

540.0

540.0

540.0

540.0

540.0

minutes. When-

ever an Input is out of range (

UFL

UFL

UFL

UFL

UFL

or

OFL

OFL

OFL

OFL

OFL

displayed), shorted,

or open the timer will start. When the time has elapsed, the
instrument will disable the output(s) and display

bAd InP

bAd InP

bAd InP

bAd InP

bAd InP

.

If

OFF

is selected, the Input Fault Timer will not be recog-

nized (time = infinite).

SEn2

SEn2

SEn2

SEn2

SEn2

Sensor Rate of Change: Select

OFF

OFF

OFF

OFF

OFF

,

1

11

11

to

4000

4000

4000

4000

4000

°F, °C, or

counts per 1 second period. This value is usually set to be
slightly greater than the fastest process response expected
during a 1 second period, but measured for at least 2
seconds. If the process is faster than this setting, the

SEn2

bAd

error message will appear. The outputs will then be

turned off. This function can be used to detect a runaway
condition, or speed up detection of an open thermocouple.
Use the INDEX & ENTER keys to reset.

SCL2

SCL2

SCL2

SCL2

SCL2

Scale Low: Select 100 to 9999 counts below

SCH2

SCH2

SCH2

SCH2

SCH2

. The total

span between

SCL2

SCL2

SCL2

SCL2

SCL2

and

SCH2

SCH2

SCH2

SCH2

SCH2

must be within 11998 counts.

Maximum setting range is

-1999

to +

9999

counts. Minimum

span is 100 counts. For Current and Voltage inputs, this will
set the low range end. Viewable only for Thermocouple and
RTD ranges.