Dwyer 32DZ User Manual
Page 19
June, 2000
Page 19 of 40
949-1318
OFF
OFF
OFF
OFF
OFF
Reset Offset Value is retained in memory when the
process input is not within the Proportional Band.
Art1
Art1
Art1
Art1
Art1
Approach Rate Time: Select
OFF
OFF
OFF
OFF
OFF
,
0.01
0.01
0.01
0.01
0.01
to
99.99
99.99
99.99
99.99
99.99
minutes. The
function defines the amount of Rate applied when the input
is outside of the Proportional Band. The
Art1
time and the
rtE1
time are independent and have no effect on each other.
To increase damping effect and reduce overshoot set the
approach rate time for a value greater than the natural rise
time of the process (natural rise time = process value time
to set point).
Fi 1
Fi 1
Fi 1
Fi 1
Fi 1
Fuzzy Logic Intensity: Select
0
00
00
to
100
100
100
100
100
%.
0
% is OFF
(disables Fuzzy Logic). The function defines the amount of
impact Fuzzy Logic will have on the output. If
Fi 1
Fi 1
Fi 1
Fi 1
Fi 1
is set
to
0
00
00
,
Fbd1
Fbd1
Fbd1
Fbd1
Fbd1
and
Frt1
Frt1
Frt1
Frt1
Frt1
below will not appear.
Fbd1
Fbd1
Fbd1
Fbd1
Fbd1
Fuzzy Logic Error Band: Select
0
00
00
to
4000
4000
4000
4000
4000
°F, °C, or counts.
Sets the bandwidth of the Fuzzy Logic. Set
Fbd1
Fbd1
Fbd1
Fbd1
Fbd1
equal to
PID proportional band (
Pb1
Pb1
Pb1
Pb1
Pb1
) for best results. Self Tune,
when used, calculates this value. Will not appear if
Fi 1
Fi 1
Fi 1
Fi 1
Fi 1
is
0
00
00
.
Frt1
Frt1
Frt1
Frt1
Frt1
Fuzzy Logic Rate of Change: Select
0.00
0.00
0.00
0.00
0.00
to
99.99
99.99
99.99
99.99
99.99
counts/
second. For best initial setting, find the count/second
change of process value near Set Point 1 with output ON
(100% output). Multiply this value by 3. Set
Frt1
Frt1
Frt1
Frt1
Frt1
to this
calculated value. Self Tune, when used, calculates this
value. Will not appear if
Fi 1
Fi 1
Fi 1
Fi 1
Fi 1
is
0
00
00
.
PEA1
PEA1
PEA1
PEA1
PEA1
The Peak feature stores the highest input the control has
measured for Zone 1 since the last reset or Power On. At
Power On,
PEA1
is reset to the present input value. To
manually reset the value
PEA1
PEA1
PEA1
PEA1
PEA1
must be in the lower display.
Press the ENTER key to reset.
PEA1
PEA1
PEA1
PEA1
PEA1
will be reset and
display the present input value.
UAL1
UAL1
UAL1
UAL1
UAL1
The Valley feature stores the lowest input the Instrument
has measured for Zone 1 since the last reset or Power On.
At Power On,
UAL1
UAL1
UAL1
UAL1
UAL1
is reset to the present input. To manually
reset the value
UAL1
UAL1
UAL1
UAL1
UAL1
must be in the lower display. Press
the ENTER key.
UAL1
UAL1
UAL1
UAL1
UAL1
will be reset and display the present
input value.