Dwyer 32DZ User Manual
Page 20
949-1318
Page 20 of 40
June, 2000
InC1
InC1
InC1
InC1
InC1
Input Correction: Select
-500
-500
-500
-500
-500
to
500
500
500
500
500
°F, °C, or counts. This
feature allows the input value to be changed to agree with
an external reference or to compensate for sensor error.
Note:
InC1
is reset to zero when the input type is changed,
or when decimal position is changed.
FiL1
FiL1
FiL1
FiL1
FiL1
Digital Filter: Select
OFF
OFF
OFF
OFF
OFF
,
1
11
11
to
99
99
99
99
99
. In some cases the time
constant of the sensor, or noise could cause the display to
jump enough to be unreadable. A setting of
2
is usually
sufficient to provide enough filtering for most cases, (
2
represents approximately a 1 second time constant). When
the 0.1 degree resolution is selected this should be in-
creased to
4
. If this value is set too high, controllability will
suffer.
LPb1
LPb1
LPb1
LPb1
LPb1
Loop Break Protection: Select
OFF
OFF
OFF
OFF
OFF
,
1
11
11
to
9999
9999
9999
9999
9999
seconds. If,
during operation, the output is minimum (0%) or maximum
(100%), and the input moves less than 5°F (3°C) or 5 counts
over the time set for
LPb1
, the
LOOP bAd
LOOP bAd
LOOP bAd
LOOP bAd
LOOP bAd
message will
appear. The loop break error can be reset by pressing the
ENTER key when at the
LPb1
menu item. The INDEX &
ENTER keys may also be used.
If
Edit
Edit
Edit
Edit
Edit
is set to
1
11
11
, jump to
LorE
LorE
LorE
LorE
LorE
on page 24.
If
Edit
Edit
Edit
Edit
Edit
is set to
3
33
33
, continue.