Program setup and operation, Operation and programming of options, Option 992, serial communication – Dwyer 32DZ User Manual
Page 13
June, 2000
Page 13 of 40
949-1318
The calculations for the PID values are the same as used in the standard Ziegler
- Nichols equations that have been recognized as standard for decades.
The only modification to the application of the Ziegler - Nichols equations is
controlled by the
dFC1
dFC1
dFC1
dFC1
dFC1
and
dfC2
dfC2
dfC2
dfC2
dfC2
menu items. These menu items control the
amount of rate (derivative) that is applied. A
dFC1
dFC1
dFC1
dFC1
dFC1
or
dfC2
dfC2
dfC2
dfC2
dfC2
setting of
3
33
33
(factory
default) or less allows for less damping. A
dFC1
dFC1
dFC1
dFC1
dFC1
or
dfC2
dfC2
dfC2
dfC2
dfC2
setting of
4
44
44
allows
for critical damping as set forth in Ziegler - Nichols. A
dFC1
dFC1
dFC1
dFC1
dFC1
or
dfC2
dfC2
dfC2
dfC2
dfC2
setting
of
5
55
55
or more allows over damping of the process.
Program Setup and Operation
In the secondary menu set
tun1
tun1
tun1
tun1
tun1
or
tun2
tun2
tun2
tun2
tun2
to
SELF
SELF
SELF
SELF
SELF
. Skip
Lrn1
Lrn1
Lrn1
Lrn1
Lrn1
/
Lrn2
Lrn2
Lrn2
Lrn2
Lrn2
and check
to make sure that
dFC1
dFC1
dFC1
dFC1
dFC1
/
dfC2
dfC2
dfC2
dfC2
dfC2
is (are) set to the desired value. Back up to
Lrn1
Lrn1
Lrn1
Lrn1
Lrn1
/
lrn2
lrn2
lrn2
lrn2
lrn2
and set to
YES
YES
YES
YES
YES
. The control will begin the Self Tune function.
While the Self Tune function is active, the right hand decimal point on the
lower display will blink. When Self Tune is complete, the blinking will stop.
After Self Tune is complete, the
tun1
tun1
tun1
tun1
tun1
/
tun2
tun2
tun2
tun2
tun2
setting(s) automatically
switch(es) to
PID
PID
PID
PID
PID
. This allows examination and / or modification of the
values calculated. We recommend that you do not change the calculated
values unless you have a firm understanding of the parameters involved and
their function. For more information on PID tuning, please contact your
supplier.
OPERATION AND PROGRAMMING OF OPTIONS
Option 992, Serial Communication.
The serial communications option allows the control to be written to and read
from a remote computer or other similar digital device. Communication is
allowed through a RS-485 (Option 992) port.
See Wiring for Optional Inputs and Outputs for information on wiring the
communication lines. Wiring for the RS-485 is run from control to control in
a daisy chain fashion with a termination resistor (120 ohms) across the
transmit and receive terminals of the last control in the chain.
Select the control address and communication baud rate with the
Addr
Addr
Addr
Addr
Addr
and
bAUd
bAUd
bAUd
bAUd
bAUd
menu items in the Secure Menu. The address for Zone 1 will be the
address selected. The address for Zone 2 will be the address selected for Zone
1 plus one. For example, if
Addr
Addr
Addr
Addr
Addr
is set to
1E
, Zone 1 parameters will be
addressed through address
1E
and Zone 2 parameters will be addressed
through address
1F
.