Easicool™eze precision air conditioning, Te ch nic al x-t yp e v, Technical data upflow units x type – Airedale EasiCool 6kW 64kW User Manual
Page 93: V35x - v40x, Electrical data

EasiCool™EZE
Precision Air Conditioning
93
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Te
ch
nic
al
X-T
yp
e
V
V35X - V40X
Technical Data Upflow Units X Type
Electrical Data
Mechanical
(1)
Entering air 24°C/45% RH ambient 35°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
For refrigerant charges, refer to
Unit Refrigerant Charge (kg/Circuit)
.
(6)
Based on air temperature of 15.5°C leaving the evaporator coil.
(7)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard
forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional
data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
V35X-EZE-0
V35X2-EZE-0
Standard Condenser Match
CS50
CS50
Unit Data Full Function
(1)
Nominal Run Amps
A
76.3
75.6
Maximum Start Amps
A
202.2
140.4
Recommended Mains Fuse Size
A
100
100
Unit Data Cooling Only
(2)
Nominal Run Amps
A
33.0
32.3
Maximum Start Amps
A
158.9
97.1
Recommended Mains Fuse Size
A
40
40
Max Mains Incoming Cable Size
mm²
35
35
Mains Supply
V
400V / 3PH + N / 50HZ
Control Circuit
VAC
24
24
Evaporator Fan - Per Fan
Maximum Electrical Input Power
(3)
kW
1 x 4
1 x 4
Full Load Amps
A
8.12
8.12
Locked Rotor Amps
A
60.9
60.9
Compressor - Per Compressor
Quantity x Motor Size
kW
1 x 11
2 x 6.5
Nominal Run Amps
A
19.1
9.2
Locked Rotor Amps
A
145
74
Type of Start
Direct On Line
Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size
kW
2 x 0.6
2 x 0.6
Full Load Amps
A
2.62
2.62
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
3
3
Number of Elements
9
9
Rating
kW
30
30
Curent per Phase
A
43.30
43.30
Humidifier
Capacity
kg/hr
15
15
Rating
kW
11.25
11.25
Full Load Amps
A
16.24
16.24