Easicool™eze precision air conditioning, Technical data upflow units wx type, Te ch nic al w x - t yp e v – Airedale EasiCool 6kW 64kW User Manual
Page 119: Performance data

EasiCool™EZE
Precision Air Conditioning
Technical Data Upflow Units WX Type
Performance Data
Cooling Capacity (1)
Condenser Entering/Leaving Temperature - Based on 5°C ΔT
Air On
25°C/30°C
30°C/35°C
35°C/40°C
40°C/45°C
(DB°C/%RH) TC (kW) SC (kW)
THR
(kW)
TC (kW) SC (kW)
THR
(kW)
TC (kW) SC (kW)
THR
(kW)
TC (kW) SC (kW)
THR
(kW)
V28WX2-EZE
22/50
31.8
29.0
34.9
30.7
28.4
35.7
29.5
27.8
36.4
28.2
27.1
37.2
24/45
32.7
31.5
35.8
31.5
30.8
36.6
30.3
30.2
37.3
29.0
29.0
38.1
26/40
32.5
32.5
35.8
31.3
31.3
36.7
30.2
30.2
37.5
29.2
29.2
38.4
V31WX-EZE
22/50
33.7
32.1
36.9
32.5
31.4
37.7
31.2
30.7
38.5
29.8
29.8
39.3
24/45
34.7
34.7
38.0
33.5
33.5
38.8
32.2
32.2
39.5
30.8
30.8
40.3
26/40
35.4
35.4
38.7
34.2
34.2
39.5
32.9
32.9
40.3
31.5
31.5
41.1
V31WX2-EZE
22/50
36.2
33.5
39.7
35.0
32.8
40.7
33.7
32.1
41.7
32.2
31.2
42.8
24/45
37.3
36.2
40.8
36.1
35.5
41.8
34.7
34.7
42.8
33.2
33.2
43.8
26/40
38.0
38.0
41.5
36.7
36.7
42.5
35.4
35.4
43.5
33.9
33.9
44.6
V35WX-EZE
22/50
40.0
38.0
43.7
38.6
37.2
44.7
37.0
36.3
45.7
35.3
35.3
46.7
24/45
41.2
41.2
45.0
39.7
39.7
46.0
38.1
38.1
46.9
36.4
36.4
48.0
26/40
42.1
42.1
45.9
40.6
40.6
46.9
39.0
39.0
47.8
37.2
37.2
48.8
V35WX2-EZE
22/50
39.4
37.6
43.0
37.9
36.8
43.7
36.2
35.9
44.4
34.4
34.4
45.2
24/45
40.6
40.6
44.3
39.0
39.0
44.9
37.3
37.3
45.6
35.5
35.5
46.4
26/40
41.5
41.5
45.2
39.9
39.9
45.8
38.1
38.1
46.5
36.3
36.3
47.2
V40WX-EZE
22/50
43.9
42.2
48.0
42.3
41.3
49.2
40.7
40.5
50.5
39.1
39.1
51.8
24/45
45.9
45.9
50.0
44.5
44.5
51.3
42.9
42.9
52.6
41.2
41.2
53.9
26/40
47.0
47.0
51.2
45.6
45.6
52.4
44.0
44.0
53.7
42.3
42.3
55.1
V40WX2-EZE
22/50
42.3
41.4
46.3
40.5
40.4
47.4
38.9
38.9
48.6
37.2
37.2
49.8
24/45
44.4
44.4
48.4
42.8
42.8
49.5
41.1
41.1
50.6
39.2
39.2
51.7
26/40
45.5
45.5
49.6
43.9
43.9
50.7
42.2
42.2
51.8
40.4
40.4
53.0
V45WX2-EZE
22/50
46.6
43.6
50.2
44.8
42.7
51.4
42.8
41.6
52.7
40.8
40.6
53.9
24/45
47.9
47.3
51.6
46.1
46.1
52.8
44.1
44.1
54.0
42.0
42.0
55.2
26/40
49.0
49.0
52.8
47.2
47.2
53.9
45.2
45.2
55.2
43.1
43.1
56.3
V50WX2-EZE
22/50
57.6
51.8
62.0
55.7
50.7
63.7
53.6
49.6
65.5
51.4
48.4
67.3
24/45
57.7
55.8
62.2
55.6
54.6
64.0
53.5
53.4
65.8
51.5
51.5
67.6
26/40
60.4
60.3
65.0
58.5
58.5
66.7
56.3
56.3
68.4
54.1
54.1
70.2
V55WX2-EZE
22/50
63.5
55.1
68.4
61.3
53.9
70.2
58.8
52.6
72.2
56.4
51.3
74.1
24/45
65.2
59.4
70.2
63.0
58.3
72.0
60.5
57.0
73.9
58.0
55.8
75.8
26/40
66.7
64.0
71.8
64.4
62.8
73.6
61.9
61.5
75.4
59.3
59.3
77.2
V60WX2-EZE
22/50
67.5
59.1
72.7
65.1
57.8
74.7
62.5
56.5
76.7
59.8
55.1
78.7
24/45
69.2
63.9
74.6
66.8
62.7
76.5
64.2
61.3
78.5
61.4
59.9
80.4
26/40
72.6
70.1
78.2
70.5
69.0
80.5
68.2
67.8
82.9
65.9
65.9
85.2
TC = Total Cooling
SC = Sensible Cooling
THR = Total Heat Rejection
(1) All data quoted is gross
(2) Interpolate for water temperatures between those quoted, do not extrapolate
(3) Water flow rate (l/s) = THR/(4.19*ΔT) at 100% Water; for glycol use refer to Ethylene Glycol
Correction Factors section
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55%
Condenser Minimum Entering Temperature °C
+25°C
Condenser Maximum Leaving Water Temperature °C +45°C
119
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013