Easicool™eze precision air conditioning, Performance data standard condenser, Operating limits – Airedale EasiCool 6kW 64kW User Manual
Page 57

EasiCool™EZE
Precision Air Conditioning
Cooling Capacity (1)
Ambient
Air On
25°C
30°C
35°C
40°C
(DB°C/%RH)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
DF28X-EZE C45
22/50
28.7
26.7
26.7
25.6
26.4
25.5
25
24.8
24/45
29.4
29
27.4
27.4
27.1
27.1
25.7
25.7
26/40
29.2
29.2
27.4
27.4
27.1
27.1
26.1
26.1
DF31X-EZE C45
22/50
31.9
30.4
30.2
29.4
29.5
29
27.9
27.9
24/45
32.9
32.9
31.1
31.1
30.3
30.3
28.7
28.7
26/40
33.4
33.4
31.8
31.8
30.9
30.9
29.3
29.3
DF35X-EZE CS50
22/50
38.1
36.1
36.1
34.9
35.2
34.4
33.6
33.6
24/45
39.1
39.1
37.1
37.1
36.3
36.3
34.6
34.6
26/40
40
40
38
38
37
37
35.3
35.3
DF40X-EZE CS50
22/50
41.6
40
39.7
38.9
38.5
38.3
37.1
37.1
24/45
43.4
43.4
41.7
41.7
40.4
40.4
38.8
38.8
26/40
44.3
44.3
42.7
42.7
41.4
41.4
39.8
39.8
DF45X-EZE CS50
22/50
46.2
42.4
44.5
41.5
42.6
40.5
40.7
39.4
24/45
47.4
45.8
45.6
44.9
43.8
43.8
41.8
41.8
26/40
48.4
48.4
46.6
46.6
44.7
44.7
42.7
42.7
DF50X2-EZE CS65
22/50
54.6
49.1
51.9
47.7
50.6
46.9
48.4
45.6
24/45
54.6
52.8
51.8
51.3
50.5
50.5
48.6
48.6
26/40
57.1
57.1
54.6
54.6
52.9
52.9
50.8
50.8
DF55X2-EZE CS80
22/50
60.8
52.5
57.4
50.8
56.3
50.2
54
48.9
24/45
62.3
56.5
59
54.8
57.8
54.2
55.4
53
26/40
63.8
60.8
60.4
59.1
59.1
58.4
56.7
56.7
DF60X2-EZE CS80
22/50
64.4
56.2
61
54.5
59.5
53.7
57
52.3
24/45
65.9
60.7
62.6
59
61.1
58.1
58.4
56.8
26/40
68.6
66.2
66
64.9
64.4
64
62.2
62.2
57
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Te
ch
nic
al
X-T
yp
e
DF
Technical Data Downflow Units X Type
Performance Data
Standard Condenser
TC = Total Cooling
SC = Sensible Cooling
(1) All data quoted is gross
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55% (based upon 24°C Dry Bulb)
Outdoor Temperature
-20°C to +41°C