Easicool™eze precision air conditioning, Technical data downflow units wx type, Te ch nic al w x - t yp e df – Airedale EasiCool 6kW 64kW User Manual
Page 115

EasiCool™EZE
Precision Air Conditioning
Technical Data Downflow Units WX Type
Electrical Data
115
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Te
ch
nic
al
W
X - T
yp
e
DF
DF50WX2 - DF60WX2
Mechanical
(1)
Entering air 24°C/45% RH condenser water in / out: 30°C/35°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
For refrigerant charges, refer to
Unit Refrigerant Charge (kg/Circuit)
.
(6)
Based on air temperature of 15.5°C leaving the evaporator coil.
(7)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water (Optional Extra) - X & WX Models
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard
forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional
data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
DF50WX2-EZE-0
DF55WX2-EZE-0
DF60WX2-EZE-0
Unit Data Full Function
(1)
Nominal Run Amps
A
84.5
82.1
88.4
Maximum Start Amps
A
198.8
187.6
192.3
Recommended Mains Fuse Size
A
100
100
100
Unit Data Cooling Only
(2)
Nominal Run Amps
A
41.2
38.8
45.1
Maximum Start Amps
A
155.5
144.3
149.0
Recommended Mains Fuse Size
A
50
50
63
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50HZ
Control Circuit
VAC
24
24
24
Evaporator Fan - Per Fan
Maximum Electrical Input Power
(3)
kW
2 x 2.2
2 x 2.2
2 x 3
Full Load Amps
A
4.64
4.64
6.18
Locked Rotor Amps
A
32.5
32.5
43.3
Compressor - Per Compressor
Quantity x Motor Size
kW
2 x 7.8
2 x 8.5
2 x 9.7
Nominal Run Amps
A
15.7
14.5
16.1
Locked Rotor Amps
A
130
120
120
Type of Start
Direct On Line
Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size
kW
2 x 0.6
3 x 0.6
3 x 0.6
Full Load Amps
A
2.62
2.62
2.62
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
3
3
3
Number of Elements
9
9
9
Rating
kW
30
30
30
Curent per Phase
A
43.30
43.30
43.30
Humidifier
Capacity
kg/hr
15
15
15
Rating
kW
11.25
11.25
11.25
Full Load Amps
A
16.24
16.24
16.24