EasiCool™EZE
Precision Air Conditioning
DF26X - DF31X
69
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Te
ch
nic
al
X-T
yp
e
DF
Technical Data Downflow Units X Type
Electrical Data
Mechanical
(1)
Entering air 24°C/45% RH ambient 35°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
For refrigerant charges, refer to
Unit Refrigerant Charge (kg/Circuit)
.
(6)
Based on air temperature of 15.5°C leaving the evaporator coil.
(7)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard
forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional
data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
DF26X-EZE-0
DF28X-EZE-0
DF31X-EZE-0
Standard Condenser Match
C45
C45
C45
Unit Data Full Function
(1)
Nominal Run Amps
A
56.4
57.7
63.6
Maximum Start Amps
A
164.6
165.9
180.3
Recommended Mains Fuse Size
A
63
80
80
Unit Data Cooling Only
(2)
Nominal Run Amps
A
23.9
25.2
31.2
Maximum Start Amps
A
132.1
133.4
147.9
Recommended Mains Fuse Size
A
32
32
40
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
Mains Supply
Control Circuit
VAC
24
24
24
Evaporator Fan - Per Fan
Maximum Electrical Input Power
(3)
kW
1 x 1.5
1 x 2.2
1 x 4
Full Load Amps
A
3.39
4.64
8.12
Locked Rotor Amps
A
23.1
32.5
60.9
Compressor - Per Compressor
Quantity x Motor Size
kW
1 x 8.3
1 x 8.3
1 x 9.73
Nominal Run Amps
A
14.8
14.8
17.3
Locked Rotor Amps
A
123
123
134
Type of Start
Direct On Line
Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size
kW
2 x 0.6
2 x 0.6
2 x 0.6
Full Load Amps
A
2.62
2.62
2.62
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
3
3
3
Number of Elements
8
8
8
Rating
kW
20
20
20
Curent per Phase
A
32.48
32.48
32.48
Humidifier
Capacity
kg/hr
8
8
8
Rating
kW
6
6
6
Full Load Amps
A
8.66
8.66
8.66