Easicool™eze precision air conditioning, Dimensional & installation data, Ins ta lla tio n – Airedale EasiCool 6kW 64kW User Manual
Page 40: Weights downflow

EasiCool™EZE
Precision Air Conditioning
(1)
Weights quoted for units fitted with the standard Forward curved EC fan motor
include the cooling fan weight within the unit cabinet (AHU).
(2)
Weights quoted for units fitted with the optional Backward Curved EC fan motor
exclude the cooling fan weight within the unit cabinet (AHU).
(3)
Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.
Dimensional & Installation Data
Weights
Downflow
Standard Evaporator
Fan - Fwd EC Motor
Optional Evaporator
Fan - Bkwd EC Motor
Machine
(AHU)
(3
)
Operating
(AHU)
Machine
(AHU)
(3
)
Operating
(AHU)
Floorstand
DF6X
kg
194
176
26
DF8X
kg
195
179
26
DF10X
kg
199
187
26
DF13X
kg
217
206
29
DF15X
kg
241
213
29
DF17X
kg
242
214
29
DF20X2
kg
293
267
44
DF22X2
kg
293
267
44
DF26X2
kg
293
267
44
DF28X
kg
424
380
125
DF31X
kg
420.8
375
125
DF35X
kg
478.8
430
128
DF40X
kg
506.5
439
128
DF45X
kg
559.5
492
128
DF50X2
kg
641
562
190
DF55X2
kg
658
579
190
DF60X2
kg
658
573
190
Standard Evaporator
Fan - Fwd EC Motor
Optional Evaporator
Fan - Bkwd EC Motor
Machine
(AHU)
(3
)
Operating
(AHU)
Machine
(AHU)
(3
)
Operating
(AHU)
Floorstand
DF6WX
kg
210
212
192
194
26
DF8WX
kg
215
216
199
200
26
DF10WX
kg
218
219
206
207
26
DF13WX
kg
240
241
229
230
29
DF15WX
kg
271
273
243
245
29
DF17WX
kg
275
277
247
249
29
DF20WX2 kg
334
336
308
310
44
DF22WX2 kg
334
336
308
310
44
DF26WX2 kg
333
336
307
310
44
DF28WX
kg
480
486
436
442
125
DF31WX
kg
476.8
482.8
431
437
125
DF35WX
kg
538.8
544.8
490
496
128
DF40WX
kg
571.5
577.5
504
510
128
DF45WX
kg
646.5
656.5
579
589
128
DF50WX2 kg
732
742
653
663
190
DF55WX2 kg
751
761
672
682
190
DF60WX2 kg
751
761
666
676
190
40
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Ins
ta
lla
tio
n