Easicool™eze precision air conditioning, Performance data larger condenser, Operating limits – Airedale EasiCool 6kW 64kW User Manual
Page 58

EasiCool™EZE
Precision Air Conditioning
Cooling Capacity (1)
Ambient
Air On
25°C
30°C
35°C
40°C
45°C
(DB°C/%RH) TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
DF6X-EZE C15
22/50
6.8
6.0
6.1
5.7
6.1
5.7
6.0
5.7
5.7
5.6
24/45
7.0
6.6
6.3
6.3
6.3
6.3
6.2
6.2
5.9
5.9
26/40
7.1
7.1
6.4
6.4
6.4
6.4
6.3
6.3
6.0
6.0
DF8X-EZE C20
22/50
9.4
8.1
8.6
7.7
8.6
7.7
8.4
7.6
8.1
7.5
24/45
9.7
8.8
8.9
8.4
8.9
8.4
8.7
8.3
8.3
8.1
26/40
9.9
9.5
9.2
9.1
9.2
9.1
8.9
8.9
8.6
8.6
DF10X-EZE C20
22/50
10.7
9.7
9.9
9.2
9.9
9.2
9.6
9.1
9.2
8.8
24/45
11.0
10.5
10.3
10.0
10.3
10.0
9.9
9.8
9.6
9.5
26/40
11.3
11.2
10.7
10.7
10.7
10.7
10.3
10.3
10.0
10.0
DF13X-EZE C25
22/50
14.1
11.7
13.0
11.2
13.0
11.2
12.4
10.9
11.7
10.6
24/45
14.5
12.7
13.4
12.2
13.3
12.2
12.7
11.9
12.1
11.6
26/40
14.8
14.0
13.7
13.6
13.6
13.6
13.0
13.0
12.3
12.3
DF15X-EZE C35
22/50
17.2
14.1
15.7
13.4
15.7
13.4
15.1
13.2
14.3
12.9
24/45
17.7
15.3
16.2
14.7
16.2
14.7
15.5
14.4
15.0
14.2
26/40
18.0
16.6
16.6
16.0
16.6
16.0
15.9
15.7
15.2
15.2
DF17X-EZE C45
22/50
20.5
17.6
18.6
16.7
18.6
16.7
18.2
16.5
17.3
16.0
24/45
21.0
19.1
19.2
18.2
19.2
18.2
18.7
17.9
17.7
17.5
26/40
21.4
20.6
19.6
19.6
19.6
19.6
19.1
19.1
18.2
18.2
DF22X2-EZE CS50
22/50
25.6
20.6
23.4
19.6
23.4
19.6
22.7
19.3
21.8
18.9
24/45
26.8
22.5
24.7
21.5
24.7
21.5
23.9
21.2
22.9
20.7
26/40
27.6
24.3
25.5
23.3
25.5
23.3
24.6
22.9
23.5
22.5
DF25X2-EZE CS50
22/50
26.8
22.5
24.7
21.5
24.7
21.5
23.8
21.1
22.8
20.6
24/45
27.6
24.5
25.5
23.6
25.5
23.6
24.6
23.1
23.6
22.7
26/40
28.3
26.7
26.2
25.7
26.2
25.7
25.3
25.2
24.2
24.2
DF26X-EZE CS50
22/50
28.2
25.1
26.0
23.9
26.0
23.9
25.0
23.4
23.8
22.8
24/45
29.0
27.1
26.8
26.0
26.8
26.0
25.7
25.4
24.5
24.5
26/40
29.6
29.3
27.4
27.4
27.4
27.4
26.3
26.3
25.1
25.1
58
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Te
ch
ni
ca
l
X-
Ty
pe
DF
Technical Data Downflow Units X Type
Performance Data
Larger Condenser
TC = Total Cooling
SC = Sensible Cooling
(1) All data quoted is gross
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55% (based upon 24°C Dry Bulb)
Outdoor Temperature
-20°C to +41°C