Precision Air Conditioning
Cooling Capacity (1)
Ambient
Air On
25°C
30°C
35°C
40°C
(DB°C/%RH)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
DF6X-EZE C11
22/50
6.6
5.9
6.1
5.7
6.1
5.7
5.9
5.6
24/45
6.8
6.5
6.3
6.3
6.3
6.3
6
6
26/40
7
7
6.4
6.4
6.4
6.4
6.2
6.2
DF8X-EZE C15
22/50
9.3
8.1
8.6
7.7
8.6
7.7
8.3
7.6
24/45
9.5
8.7
8.9
8.4
8.9
8.4
8.5
8.2
26/40
9.8
9.4
9.2
9.1
9.1
9.1
8.8
8.8
DF10X-EZE C15
22/50
10.5
9.6
9.9
9.2
9.8
9.2
9.4
8.9
24/45
10.8
10.4
10.3
10
10.1
9.9
9.7
9.6
26/40
11.2
11.1
10.7
10.7
10.5
10.5
10.1
10.1
DF13X-EZE C20
22/50
13.9
11.6
13
11.2
12.8
11.1
12.2
10.9
24/45
14.3
12.6
13.4
12.2
13.2
12.1
12.6
11.8
26/40
14.6
13.9
13.7
13.6
13.4
13.4
12.8
12.8
DF15X-EZE C25
22/50
16.7
13.9
15.7
13.4
15.3
13.3
14.5
12.9
24/45
17
15
16.2
14.7
15.7
14.5
15
14.2
26/40
17.4
16.3
16.6
16
16
15.7
15.4
15.4
DF17X-EZE C35
22/50
20
17.4
18.6
16.7
18.5
16.6
17.6
16.2
24/45
20.5
18.8
19.2
18.2
19
18.1
18.1
17.6
26/40
20.9
20.3
19.6
19.6
19.4
19.4
18.5
18.5
DF22X2-EZE C45
22/50
25.5
20.5
23.4
19.6
23.4
19.6
22.4
19.2
24/45
26.6
22.4
24.7
21.5
24.7
21.5
23.6
21
26/40
27.4
24.2
25.5
23.3
25.4
23.3
24.2
22.8
DF25X2-EZE C45
22/50
26.6
22.4
24.7
21.5
24.7
21.5
23.5
20.9
24/45
27.4
24.4
25.5
23.6
25.4
23.5
24.3
23
26/40
28.1
26.6
26.2
25.7
26.1
25.6
24.9
24.9
DF26X-EZE C45
22/50
28
25
26
23.9
25.8
23.8
24.5
23.1
24/45
28.7
27
26.8
26
26.5
25.8
25.2
25.1
26/40
29.3
29.1
27.4
27.4
27.1
27.1
25.7
25.7
56
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Te
ch
ni
ca
l
X-
Ty
pe
DF
Technical Data Downflow Units X Type
Performance Data
Standard Condenser
TC = Total Cooling
SC = Sensible Cooling
(1) All data quoted is gross
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55% (based upon 24°C Dry Bulb)
Outdoor Temperature
-20°C to +41°C