Easicool™eze precision air conditioning, Electrical data – Airedale EasiCool 6kW 64kW User Manual
Page 67

EasiCool™EZE
Precision Air Conditioning
DF22X2 - DF25X2
67
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Te
ch
nic
al
X-T
yp
e
DF
Technical Data Downflow Units X Type
Electrical Data
Mechanical
(1)
Entering air 24°C/45% RH ambient 35°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
For refrigerant charges, refer to
Unit Refrigerant Charge (kg/Circuit)
.
(6)
Based on air temperature of 15.5°C leaving the evaporator coil.
(7)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard
forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional
data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
DF22X2-EZE-0
DF25X2-EZE-0
Standard Condenser Match
C45
C45
Unit Data Full Function
(1)
Nominal Run Amps
A
39.9
39.9
Maximum Start Amps
A
83.4
83.4
Recommended Mains Fuse Size
A
50
50
Unit Data Cooling Only
(2)
Nominal Run Amps
A
18.2
18.2
Maximum Start Amps
A
61.7
61.7
Recommended Mains Fuse Size
A
25
25
Max Mains Incoming Cable Size
mm²
35
35
Mains Supply
V
400V / 3PH + N / 50HZ
Control Circuit
VAC
24
24
Evaporator Fan - Per Fan
Maximum Electrical Input Power
(3)
kW
2 x 1.15
2 x 1.15
Full Load Amps
A
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
Compressor - Per Compressor
Quantity x Motor Size
kW
2 x 4.7
2 x 4.7
Nominal Run Amps
A
6.5
6.5
Locked Rotor Amps
A
50
50
Type of Start
Direct On Line
Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size
kW
2 x 0.6
2 x 0.6
Full Load Amps
A
2.62
2.62
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
2
2
Number of Elements
6
6
Rating
kW
15
15
Curent per Phase
A
21.65
21.65
Humidifier
Capacity
kg/hr
3
3
Rating
kW
2.25
2.25
Full Load Amps
A
3.25
3.25