Easicool™eze precision air conditioning, Te ch nic al x-t yp e v, Technical data upflow units x type – Airedale EasiCool 6kW 64kW User Manual
Page 83: V6x - v10x, Electrical data

EasiCool™EZE
Precision Air Conditioning
V6X-EZE-0
V8X-EZE-0
V10X-EZE-0
Standard Condenser Match
C11
C15
C15
Unit Data Full Function
(1)
Nominal Run Amps
A
19.7
21.1
21.1
Maximum Start Amps
A
40.4
56.4
61.6
Recommended Mains Fuse Size
A
25
25
25
Unit Data Cooling Only
(2)
Nominal Run Amps
A
8.8
10.3
10.3
Maximum Start Amps
A
29.6
45.6
50.8
Recommended Mains Fuse Size
A
10
16
16
Max Mains Incoming Cable Size
mm²
6
6
6
Mains Supply
V
400V / 3PH + N / 50HZ
Control Circuit
VAC
24
24
24
Evaporator Fan - Per Fan
Maximum Electrical Input Power
(3)
kW
1 x 1.3
1 x 1.3
1 x 1.15
Full Load Amps
A
5.6
5.6
4.8
Locked Rotor Amps
A
5.6
5.6
4.8
Compressor - Per Compressor
Quantity x Motor Size
kW
1 x 2
1 x 2.6
1 x 3.9
Nominal Run Amps
A
3.2
4.7
5.5
Locked Rotor Amps
A
24
40
46
Type of Start
Direct On Line
Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size
kW
1 x 0.15
2 x 0.15
2 x 0.15
Full Load Amps
A
0.65
1.3
1.3
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
1
1
1
Number of Elements
3
3
3
Rating
kW
7.5
7.5
7.5
Curent per Phase
A
10.83
10.83
10.83
Humidifier
Capacity
kg/hr
3
3
3
Rating
kW
2.25
2.25
2.25
Full Load Amps
A
3.25
3.25
3.25
83
EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013
Te
ch
nic
al
X-T
yp
e
V
V6X - V10X
Technical Data Upflow Units X Type
Electrical Data
Mechanical
(1)
Entering air 24°C/45% RH ambient 35°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
For refrigerant charges, refer to
Unit Refrigerant Charge (kg/Circuit)
.
(6)
Based on air temperature of 15.5°C leaving the evaporator coil.
(7)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard
forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional
data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.