OPERATION
4
65
OPTIWAVE 5200 C
www.krohne.com
09/2013 - 4002500101 - AD FF OPTIWAVE 5200 R01 en
FF_GAIN
FF_GAIN
FF_GAIN
FF_GAIN
Feed Forward Gain
Feed Forward Gain
Feed Forward Gain
Feed Forward Gain
R/W
The gain that the feed forward input is multiplied by before it
is added to the calculated control output.
0
FF_SCALE
FF_SCALE
FF_SCALE
FF_SCALE
Feed Forward
Feed Forward
Feed Forward
Feed Forward
Scale
Scale
Scale
Scale
R/W
The feed forward input high and low scale values, engineering
units code and number of digits to the right of the decimal
point.
-
EU at 100%
R/W
The engineering unit value which represents the upper end of
range of the associated block parameter.
100
EU at 0%
R/W
The engineering unit value which represents the lower end of
range of the associated block parameter.
0
Units Index
R/W
Device Description units code index for the engineering unit
descriptor for the associated block value.
Uninitialized
Setting:
All units are possible.
FF_VAL
FF_VAL
FF_VAL
FF_VAL
Feed Forward
Feed Forward
Feed Forward
Feed Forward
Value
Value
Value
Value
R
The feed forward value and status.
-
Status
R
Status of FF_VAL
-
Value
R
Value of FF_VAL
-
GAIN
GAIN
GAIN
GAIN
Gain
Gain
Gain
Gain
R/W
Dimensionless value used by the block algorithm in
calculating the block output.
0
GRANT_DENY
GRANT_DENY
GRANT_DENY
GRANT_DENY
Grant Deny
Grant Deny
Grant Deny
Grant Deny
R/W
Options for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
-
Grant
R/W
Depending on the philosophy of the plant, the operator or a
higher level device (HLD), or a local operator's panel (LOP) in
the case of Local, may turn on an item of the Grant attribute -
Program, Tuning, Alarm or Local.
No option selected
Setting:
•
Program: Host may change mode, setpoint or output of
block
•
Tune: Host may change the tuning parameters of block
•
Alarm: Host may change the alarm parameters of block
•
Local: A local panel or handheld device may change the
target mode, setpoint or output
Deny
R/W
The "Denied" attribute is provided for use by a monitoring
application in an interface device and may not be changed by
an operator.
No option selected
Setting:
•
Program denied: Granting of program permission has been
reset
•
Tune denied: Granting of tune permission has been reset
•
Alarm denied: Granting of alarm permission has been reset
•
Local denied: Granting of local permission has been reset
HI_ALM
HI_ALM
HI_ALM
HI_ALM
High Alarm
High Alarm
High Alarm
High Alarm
Mix
The status for High Alarm and its associated time stamp.
-
Unacknowledged
R/W
A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value