OPERATION

38

OPTIWAVE 5200 C

www.krohne.com

09/2013 - 4002500101 - AD FF OPTIWAVE 5200 R01 en

IO_OPTS

IO_OPTS

IO_OPTS

IO_OPTS

IO Options

IO Options

IO Options

IO Options

(IO = Input/Output)

(IO = Input/Output)

(IO = Input/Output)

(IO = Input/Output)

RW

Options which the user may select to alter input and output

block processing.

Uninitialized

Setting:

Low Cutoff / Units Conversion

L_TYPE

L_TYPE

L_TYPE

L_TYPE

Linearization Type

Linearization Type

Linearization Type

Linearization Type

RW

Determines if the values passed by the TB to the AI block may

be used directly (Direct) or if the value is in different units and

must be converted linearly (Indirect) , or with square root (Ind

Sqr Root), using the input range defined for the transducer and

the associated output range.

Uninitialized

Setting:

Uninitialized / Direct / Indirect / Ind Sqr Root

LO_ALM

LO_ALM

LO_ALM

LO_ALM

Low Alarm

Low Alarm

Low Alarm

Low Alarm

The status for Low Alarm and its associated time stamp.

For settings of the 5 sub-elements, refer to the

"Unacknowledged", "Alarm State", "Time Stamp", "Subcode"

and "Value" items that follow.

-

LO_LO_ALM

LO_LO_ALM

LO_LO_ALM

LO_LO_ALM

Low Low Alarm

Low Low Alarm

Low Low Alarm

Low Low Alarm

The status for Low Low Alarm and its associated time stamp.

For settings of the 5 sub-elements, refer to the

"Unacknowledged", "Alarm State", "Time Stamp", "Subcode"

and "Value" items that follow.

-

Settings of 5 sub-elements for the parameters "Low Alarm" and "Low Low Alarm":

UNACKNOWLEDGED

Unacknowledged

RW

Setting:

Uninitialized / Acknowledged / Unacknowledged

Uninitialized

ALARM_STATE

Alarm State

R

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

Uninitialized

TIME_STAMP

Time Stamp

R

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Uninitialized

SUB_CODE

Subcode

R

Setting:

Other/ Block Configuration / Link Configuration / Simulation

Active / Local Override / Device Fault State / Device

Maintenance / Input Failure / Output Failure / Memory

Failure / Lost Static Data / Lost NV Data / Readback Check /

Maintenance Needed / Power Up / Out Of Service

Other

VALUE

Float Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

LO_LIM

LO_LIM

LO_LIM

LO_LIM

Low Limit

Low Limit

Low Limit

Low Limit

R

The setting for Low Alarm in engineering units.

For the setting range, refer to the " x_y_LIM" item that follows.

(-NaN)

LO_LO_LIM

LO_LO_LIM

LO_LO_LIM

LO_LO_LIM

Low Low Limit

Low Low Limit

Low Low Limit

Low Low Limit

RW

The setting for Low Low Alarm in engineering units.

For the setting range, refer to the " x_y_LIM" item that follows.

(-NaN)

LO_PRI

LO_PRI

LO_PRI

LO_PRI

Low Priority

Low Priority

Low Priority

Low Priority

RW

Priority of the Low Alarm.

For the setting range, refer to the " x_y_PRI" item that follows.

0

LO_LO_PRI

LO_LO_PRI

LO_LO_PRI

LO_LO_PRI

Low Low Priority

Low Low Priority

Low Low Priority

Low Low Priority

RW

Priority of the Low Low Alarm.

For the setting range, refer to the " x_y_PRI" item that follows.

0

Setting range for the

parameters "Low Low Limit"

and "Low Limit":

x_y_LIM

x_y_Limit

-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)

Setting range for the

parameters "Low Low Priority"

and "Low Priority":

x_y_PRI

x_y_Priority

Setting:

0...15

0

Parameter

Parameter

Parameter

Parameter
DD name

Access Description and settings

Initial Value