beautypg.com

Operation – KROHNE OPTIWAVE 5200 FOUNDATION FIELDBUS User Manual

Page 15

background image

OPERATION

4

15

OPTIWAVE 5200 C

www.krohne.com

09/2013 - 4002500101 - AD FF OPTIWAVE 5200 R01 en

UNACKNOWLEDGED

Unacknowledged

RW

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

ALARM_STATE

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

SUB_CODE

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

Other

Setting:

Other / Block Configuration / Link Configuration / Simulation

Active / Local Override / Device Fault State / Device

Maintenance / Input Failure / Output Failure / Memory

Failure / Lost Static Data / Lost NV Data / Readback Check /

Maintenance Needed / Power Up / Out Of Service

VALUE

Value

R

The value of the associated parameter at the time the alert

was detected.

0

Setting:

0...255

CLR_FSTATE

CLR_FSTATE

CLR_FSTATE

CLR_FSTATE

Clear Fault State

Clear Fault State

Clear Fault State

Clear Fault State

R/W

Writing a "Clear" to this parameter will clear the device fault

state if the field condition, if any, has cleared.

Off

Setting:

Uninitialized / Off / Clear

CONFIRM_TIME

CONFIRM_TIME

CONFIRM_TIME

CONFIRM_TIME

Confirm Time

Confirm Time

Confirm Time

Confirm Time

RW

The minimum time between retries of alert reports.

640000

Setting:

0...4294967295 in [1/32 ms]

CYCLE_SEL

CYCLE_SEL

CYCLE_SEL

CYCLE_SEL

Cycle Selection

Cycle Selection

Cycle Selection

Cycle Selection

RW

Used to select the block execution method for this resource.

Uninitialized

Setting:

Scheduled / Block execution

CYCLE_TYPE

CYCLE_TYPE

CYCLE_TYPE

CYCLE_TYPE

Cycle Type

Cycle Type

Cycle Type

Cycle Type

R

Identifies the block execution methods available for this

resource.

Scheduled

Block execution

Setting:

Scheduled / Block execution

DD_RESOURCE

DD_RESOURCE

DD_RESOURCE

DD_RESOURCE

DD Resource

DD Resource

DD Resource

DD Resource

R

String identifying the tag of the resource which contains the

Device Description for this resource.

blanks

Setting:

≤ 32 digits

DD_REV

DD_REV

DD_REV

DD_REV

DD Revision

DD Revision

DD Revision

DD Revision

R

Revision of the DD associated with the resource - used by an

interface device to locate the DD file for the resource.

Dependent on

device version.

Setting:

Dependent on device version.

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value