Operation – KROHNE OPTIWAVE 5200 FOUNDATION FIELDBUS User Manual
Page 16
4
OPERATION
16
OPTIWAVE 5200 C
www.krohne.com
09/2013 - 4002500101 - AD FF OPTIWAVE 5200 R01 en
DEV_REV
DEV_REV
DEV_REV
DEV_REV
Device Revision
Device Revision
Device Revision
Device Revision
R
Manufacturer revision number associated with the resource -
used by an interface device to locate the DD file for the
resource.
Dependent on
device version.
Setting:
Dependent on device version.
DEV_TYPE
DEV_TYPE
DEV_TYPE
DEV_TYPE
Device Type
Device Type
Device Type
Device Type
R
Manufacturer's model number associated with the resource -
used by interface devices to locate the DD file for the
resource.
OPTIWAVE5200
Setting:
OPTIWAVE5200
FAULT_STATE
FAULT_STATE
FAULT_STATE
FAULT_STATE
Fault State
Fault State
Fault State
Fault State
R
Condition set by loss of communication to an output block,
failure promoted to an output block or a physical contact.
When fault state condition is set, then output function blocks
will perform their "FSTATE" actions.
Clear
Setting:
Uninitialized / Clear / Active
FEATURES
FEATURES
FEATURES
FEATURES
Features
Features
Features
Features
R
Used to shows supported resource block options.
Reports
Soft W Lock
MVC Report
Distribution
supported
MVC
Publishing/Subcrib
ing supported
Multi-bit Alarm
(Bit-Alarm)
Support
Setting:
Reports / Faultstate / Soft W Lock / MVC Report Distribution
supported / MVC Publishing/Subcribing supported / Multi-bit
Alarm (Bit-Alarm) Support
FEATURES_SEL
FEATURES_SEL
FEATURES_SEL
FEATURES_SEL
Features Selection
Features Selection
Features Selection
Features Selection
R/W
Used to select resource block options.
Reports
Soft W Lock
Setting:
Reports / Faultstate / Soft W Lock / MVC Report Distribution
supported / MVC Publishing/Subscribing supported / Multi-bit
Alarm (Bit-Alarm) Support
FREE_SPACE
FREE_SPACE
FREE_SPACE
FREE_SPACE
Free Space
Free Space
Free Space
Free Space
R
Percent of the memory available for further configuration.
Zero in a preconfigured device.
0.0
Setting:
0.0…100.0
FREE_TIME
FREE_TIME
FREE_TIME
FREE_TIME
Free Time
Free Time
Free Time
Free Time
R
Percent of the block processing time that is free to process
additional blocks.
0.0
Setting:
0.0…100.0
GRANT_DENY
GRANT_DENY
GRANT_DENY
GRANT_DENY
Grant Deny
Grant Deny
Grant Deny
Grant Deny
R/W
Options for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
-
GRANT
Grant
RW
Depending on the philosophy of the plant, the operator or a
higher level device (HLD) or a local operator's panel (LOP) in
the case of "Local", may turn on an item of the "Grant"
attribute - Program, Tune, Alarm or Local.
Uninitialized
Setting:
Program / Tune / Alarm / Local / Operate
DENY
Deny
RW
The Denied attribute is limited for use by a monitoring
application in an interface device and may not be changed by
an operator.
Uninitialized
Setting:
Program denied / Tune denied / Alarm denied / Local denied /
Operate denied
HARD_TYPES
HARD_TYPES
HARD_TYPES
HARD_TYPES
Hardware Types
Hardware Types
Hardware Types
Hardware Types
R
The types of hardware available as channel numbers.
Scalar input
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value