beautypg.com

Operation – KROHNE OPTIWAVE 5200 FOUNDATION FIELDBUS User Manual

Page 37

background image

OPERATION

4

37

OPTIWAVE 5200 C

www.krohne.com

09/2013 - 4002500101 - AD FF OPTIWAVE 5200 R01 en

GRANT

Grant

RW

Depending on the philosophy of the plant, the operator or a

higher level device (HLD) or a local operator's panel (LOP) in

the case of "Local", may turn on an item of the "Grant"

attribute - "Program, Tune, Alarm or Local".

Uninitialized

Setting:

Program / Tune / Alarm / Local / Operate

DENY

Deny

RW

The deny attribute is provided for use by a monitoring

application in an interface device and may not be changed by

an operator.

Uninitialized

Setting:

Program denied / Tune denied / Alarm denied / Local denied /

Operate denied

HI_ALM

HI_ALM

HI_ALM

HI_ALM

High Alarm

High Alarm

High Alarm

High Alarm

The status for High Alarm and its associated time stamp.

For settings of the 5 sub-elements, refer to the

"Unacknowledged", "Alarm State", "Time Stamp", "Subcode"

and "Value" items that follow.

-

HI_HI_ALM

HI_HI_ALM

HI_HI_ALM

HI_HI_ALM

High High Alarm

High High Alarm

High High Alarm

High High Alarm

The status for High High Alarm and its associated time stamp.

For settings of the 5 sub-elements, refer to the

"Unacknowledged", "Alarm State", "Time Stamp", "Subcode"

and "Value" items that follow.

-

Settings of 5 sub-elements for the parameters "High Alarm" and "High High Alarm":

UNACKNOWLEDGED

Unacknowledged

RW

Setting:

Uninitialized / Acknowledged / Unacknowledged

Uninitialized

ALARM_STATE

Alarm State

R

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

Uninitialized

TIME_STAMP

Time Stamp

R

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Uninitialized

SUB_CODE

Subcode

R

Setting:

Other/ Block Configuration / Link Configuration / Simulation

Active / Local Override / Device Fault State / Device

Maintenance / Input Failure / Output Failure / Memory

Failure / Lost Static Data / Lost NV Data / Readback Check /

Maintenance Needed / Power Up / Out Of Service

Other

VALUE

Float Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

HI_HI_LIM

HI_HI_LIM

HI_HI_LIM

HI_HI_LIM

High High Limit

High High Limit

High High Limit

High High Limit

RW

The setting for High High Alarm in engineering units.

For the setting range, refer to the " x_y_LIM" item that follows.

NaN

HI_HI_PRI

HI_HI_PRI

HI_HI_PRI

HI_HI_PRI

High High Priority

High High Priority

High High Priority

High High Priority

RW

Priority of the High High Alarm.

For the setting range, refer to the " x_y_PRI" item that follows.

0

HI_LIM

HI_LIM

HI_LIM

HI_LIM

High Limit

High Limit

High Limit

High Limit

RW

The setting for High Alarm in engineering units.

For the setting range, refer to the " x_y_LIM" item that follows.

NaN

HI_PRI

HI_PRI

HI_PRI

HI_PRI

High Priority

High Priority

High Priority

High Priority

RW

Priority of the High Alarm.

For the setting range, refer to the " x_y_PRI" item that follows.

0

Setting range for the

parameters "High High Limit"

and "High Limit":

x_y_LIM

x_y_Limit

-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)

Setting range for the

parameters "High High Priority"

and "High Priority":

x_y_PRI

x_y_Priority

Setting:

0...15

0

Parameter

Parameter

Parameter

Parameter
DD name

Access Description and settings

Initial Value