10.3 IFC 010 Signal converter

Versions
B
- version

without display / control unit (basic version)

D - version

with display / control unit

Add-on equipment (option)

- CONFIG software and RS 232 adapter for control via

MS-DOS-PC, connection to IMoCom interface

- Hand-Held-Terminal for control of basic versions
- Other bus and computer interfaces on request

Current output
Function

- all operating data settable, galvanically isolated

Current

0 - 20 mA and 4 - 20 mA

Active output

load max. 500 ohms

Passive output

external voltage:

15 ... 20 V DC

20 ... 32 V DC

load: min. ... max.

0 ... 500

250 ... 750

Error identification

0 / 3.6 / 22 mA

Forward/reverse measurement

direction identified via status output

Pulse output
Function

- all operating data settable
- galvanically isolated
- digital pulse division, interpulse period non-uniform,

therefore if frequency meters connected allow for minimum

counting interval:

gate time, totalizer

Pulse rate for Q = 100 %

10, 100 or 1000 pulses per second (= Hz), fixed or optionally
adjustable in pulses per liter, m

3

or US gallons

(special version: up to 10 kHz scaling)

Active output:

connection: electronic totalizer (EC)
internal voltage: approx. 15 V DC, from current output
load rating: I

max

< 23 mA when operated without current output

load rating:

I

max

<

2

3 mA when operated with current output

Passive output:

connection electromechanical (EMC) or electronic (EC)
totalizers
external voltage: U

ext

30 V DC /

24 V AC

load current: I

max

150 mA

Pulse width

50, 100, 200, 500 ms or 1 s,
selectable with frequencies below 10 Hz

Forward/reverse measurement

direction identified via status output

Status output (passive)
Function

settable as indicator for flow direction, errors or trip point

Connection

external voltage: U

ext.

30 V DC /

24 V AC

load current: I

max

150 mA

Time constant

0.2 to 99.9 seconds, settable in increments of 0.1 second

Low-flow cutoff

cutoff ”on” value: 1 to 19 % of Q

100%

, adjustable in

cutoff ”off” value: 2 to 20 % 1 % increments

Local display (D versions only)

3-line LCD

Display functions

actual flowrate, forward, reverse and sum totalizers (7-digit)
or 25-character bar graph with percent display and
status messages

Display units:

actual flowrate

settable in liter/s, m

3

/h, US gallons/min or user-defined unit,

e.g. hectoliter/day or US million gallons/day

totalizers

liter, m

3

or US gallons and 1 user-defined unit

(e.g. hectoliter), selectable overflow time

Language of plain texts

English, German, French, others on request

Display:

1st (top) line

8-character, 7-segment numeral and sign display,
symbols for key acknowledgement

2nd (middle) line

10-character, 14-segment text display

3rd (bottom) line

6 markers

t

to identify display

}

1000

P

100%

[Hz]