KROHNE IFC 010 Converter EN User Manual
Page 21
4/6
Fct.
Text
Description and settings
1.04
DISPLAY
Display functions
→
DISP.FLOW
Select flow display
• NO DISP. • user unit, factory set is “Liter/hr” or “US MGal/day (see Fct. 3.05)
• m3/hr
• PERCENT
• Liter/Sec
• BARGRAPH (value and bargraph display in %)
• US.Gal/min
Press
↵
key to transfer to subfunction “DISP. TOTAL.”.
→
DISP.TOTAL.
Select totalizer display
• NO DISP. (totalizer switched on but not displayed)
• OFF (totalizer switched off)
• +TOTAL.
• –TOTAL.
• +/–TOTAL.
• SUM (
Σ
)
• ALL (displaysingle counts or all)
• m3
• Liter
• US.Gal
• user unit, factory set is “Liter” or “US MGal” (see Fct. 3.05).
Press
→
key to transfer to format setting.
Format setting
• Auto (exponent notation)
• # . #######
• ##### . ###
• ## . ######
• ###### . ##
• ### . #####
• ####### . #
• #### . ####
•
########
Press
↵
key to transfer to subfunction “DISP.MSG”.
→
DISP.MSG.
Additional messages required in measuring mode?
• NO
• YES (cyclic change with displays of measured values)
Press
↵
key to return to Fct. 1.04 DISPLAY.
1.05
CURRENT I
Current output I
→
FUNCT. I
Select function for current output I
• OFF (switched off)
• 1 DIR. (1 flow direction)
• 2 DIR. (forward/reverse flow, F/R flow measurement)
Press key
↵
, transfer to subfunction
“RANGE I”;
if
“2 DIR.”
selected, transfer to subfunction
“REV.RANGE”!
→
RANGE I
Select measuring range
• 0 - 20 mA • 4 - 20 mA (fixed ranges)
Press key
↵
to transfer to subfunction
“I ERROR“.
→
I ERROR
Select error value
• 0 mA • 3.6 mA (only with range 4-20 mA) • 22 mA
Press key
↵
to revert to
Fct. 1.05 CURRENT. I.