KROHNE IFC 010 Converter EN User Manual

Page 10

background image

Length

Type of cable, single shielding

0 - 150 m

5 - 500 ft

2

×

0.75 mm

2

Cu / 2 × 18 AWG

150 - 300 m

500 - 1000 ft

2

×

1.50 mm

2

Cu / 2 × 14 AWG

1/5

Abbreviations and explanatory notes
used in the following tables, diagrams and connection diagrams

A Signal cable A (type DS), with double shielding, see diagram for max. length

C Field current cable C, with single shielding,

type and length see Table

D High-temperature silicone cable, 3 × 1.5 mm

2

(14 AWG) Cu, with single shielding,

max. length 5 m (16 ft)

E High-temperature silicone cable, 2 × 1.5 mm

2

(14 AWG) Cu, max. length 5 m (16 ft)

L

Cable length

κκ

Electrical conductivity of the process liquid

ZD Intermediate connection box required in connection with cables D and E for primary heads

ALTOFLUX IFS 4000 F, PROFIFLUX IFS 5000 F and VARIFLUX IFS 6000 F in cases where
process temperatures exceed 150 °C (302 °F)

Recommended length of signal cable
for magnetic field frequency

1/6 × power frequency

1.3.4 Cable lengths (max. distance between signal converter and primary head)

Primary head

ECOFLUX IFS 1000 F

AQUAFLUX F

ALTOFLUX IFS 4000 F

PROFIFLUX IFS 5000 F

VARIFLUX IFS 6000 F

Meter size
DN mm

0

10

.0

-

00

15

0

25

.5

-

0

150

0

10

.0

- 1000

0

10

.0

-

0

150

200

.0

- 1000

00

2.5 -

00

15

0

25

.0

-

0

100

0

10

.5

-

00

15

0

25

.5

-

00

80

Nennweite

inch

3

/

8

-

1

/

2

1 -

0

6

3

/

8

- 40

3

/

8

-

0

6

8

- 40

1

/

10

-

1

/

2

1 -

0

4

1

/

8

0

-

1

/

2

1

-

0

3

Signal cable

A4

A3

A1

A2

A1

A4

A2
A4
A2

Field current cable C: max. length and min. cross-section

Warning: Instrument must be properly grounded to avoid personnel shock hazard.