beautypg.com

KROHNE IFC 010 Converter EN User Manual

Page 29

background image

5/4

Current output I 5.6

Fct. 1.05 CURRENT I
Press

key.

FUNCT. I = select function for current output,

press

key

OFF

(switched off, no function)

1 DIR.

(1 flow direction)

2 DIR.

(2 flow directions, F/R mode, forward/reverse)

Select using

or

key

.

Transfer to subfunction “RANGE I” with

key.

Exception: When “OFF” selected, return to Fct. 1.05 CURRENT I.

RANGE I = select measuring range,

press

key

0 - 20 mA

fixed ranges

4 - 20 mA

Press

key to transfer to number setting.

Select with key

or

.

Press key

to transfer to subfunction “I ERROR”.

I ERROR = set error value,

press

key

0

.0

mA

3.6 mA

(only possible if range ”4-20 mA” selected)

22

.6

mA

Select using key

or

.

Press

key to transfer to number setting.

Press key

to return to Fct. 1.05 CURRENT I.

Please refer to Sect. 3.2 “Factory settings”.

Refer to Sect. 2.3 for connection diagrams, and to Sect. 5.14 for characteristics.