Technical data – KROHNE H250 M40 EN User Manual

Page 78

background image

8

TECHNICAL DATA

78

H250 M40

www.krohne.com

11/2012 - 4000640702 MA H250 M40 R02 en

H250U - Vertical installation position

Reference condition for gas measurements:

Reference condition for gas measurements:

Reference condition for gas measurements:

Reference condition for gas measurements:
Flow measurements for gases are attributed to
SCFM or SCFH: Volume current in standard state 15°C - 1.013 bar abs. (ISO 13443)

Measuring span:

10 : 1

Flow values:

Values = 100%

Water 20°C / 68°F

Air: 20°C [68°F], 1,013 bar abs. [14,7 psia]

Flow direction

vertical downwards

EN

ASME

Cone

Wasser [GPH]

Luft [SCFM]

Pressure loss

[psig]

DN15

½

"

K 15.1

17.2

0.99

2.57

K 15.2

29.1

1.55

2.62

K 15.3

44.9

2.48

2.65

K 15.4

68.7

3.72

2.94

K 15.5

111

6.20

3.23

K 15.6

172

9.92

4.26

K 15.7

291

17.4

7.64

K 15.8

396

24.8

12.3

DN25

1"

K 25.1

304

18.6

1.42

K 25.2

476

27.9

1.25

K 25.3

713

43.4

1.35

K 25.4

1189

74.4

1.69

K 25.5

2008

124

2.53

DN50

2"

K 55.1

2378

149

3.23

K 55.2

3963

248

3.38

K 55.3

5548

341

3.53

INFORMATION!
The operating pressure should be at least double the pressure loss for liquids and five times for
gases. The indicated pressure losses are valid for water and air at maximum flow rate. Other
flow ranges on request. Conversion of other media or operating data is performed using the
calculation method in accordance with VDI /VDE Directive 3513.