beautypg.com

Operation – KROHNE H250 M40 EN User Manual

Page 53

background image

OPERATION

6

53

H250 M40

www.krohne.com

11/2012 - 4000640702 MA H250 M40 R02 en

END&UNIT

3.11

By changing the unit, the respective final value is scaled accordingly.

Depending on calibration, either units for volume or mass flow

measurement are available for selection.

3.11.1

FLOW RATE

For units for volume flow or mass flow, refer to

Overview of the units

ESK4-T on page 40

3.11.2

COUNTER

For units for volume counter or mass counter refer to

Overview of the

units ESK4-T on page 40

Low flow cutoff

treshold

3.12

LFC stands for L

LL

Low F

F

F

Flow C

C

C

Cutoff

To ensure a stable zero point of the current output, the current output

can be stably set to 4.00 mA 3 in a range to be selected.

3.12.1

CONTROL OFF

LFC function is not active.

CONTROL ON

LFC function is active.

3.12.2

LFC ON_VALUE

Switch-on value 1:

Value range 1 … 19% (from final value of measuring range)

Flow is greater than the switch-on value. The current output

corresponds to this.

If the flow rate falls, the current output follows until the switch-on value

1.

If the flow value continues to fall, the current output is switched to

4.00 mA 3.

Note:

Note:

Note:

Note:

The switch-on value to be set must be smaller than the previously

selected switch-off value.

3.12.3

LFC OFF_VALUE

Switch-off value 2:

Value range 2 … 20% (from the measuring range final value)

The flow rate is 0. The current output is 4.00 mA 3.

If the flow rate increases, the current output remains at 4.00 mA until it

has reached the switch-off value 2 .

Note:

Note:

Note:

Note:

The switch-off value to be set must be greater than the previously

selected switch-on value.

INP. CODE

3.13

Input code for the local operating menu

The input code is not active by default.

3.13.1

OFF

Use of an input code is not activated.

3.13.2

ON

If YES is chosen, the most recently input code must be typed in.

Factory code: → → → ^ ^ ^ ↑ ↑ ↑

If, after confirmation with YES, the → button is also pressed, then a new,

individual, nine-element code can be typed in.

The display shows the required key combination.

BASIC SETTING

3.14

Resetting parameters to factory default

There is always a safety prompt (yes/no), to avoid accidental resetting.

Label

Level Select /

Input

Explanation

MA_H250_M40_R02_en_640702_PRT.book Page 53 Wednesday, November 28, 2012 12:23 PM