beautypg.com

Appendix – KROHNE OPTISENS MAC 080 EN User Manual

Page 54

background image

9

APPENDIX

54

OPTISENS MAC 080

www.krohne.com

01/2010 - MA MAC 080 R02 en

9.2.9 Indications

The module is equipped with four LEDs mounted at the front and one LED on the board, used for
debugging purposes. The front LEDs can be mounted in two ways, either top mounted or angle
mounted. The function of the LEDs are described in the table and figure below.

Indications

Figure 9-6: Indications

1 Not used
2 Green
3 Red
4 Red

No

Indication

Description

1

Not used

-

2

Green

Indicates that the module is On-Line on the bus.

Green:

Green:

Green:

Green: Module is On-Line and data exchange is possible.

Turned Off:

Turned Off:

Turned Off:

Turned Off: Module is not On-Line.

3

Red

Indicates that the module is Off-Line on the bus.

Red:

Red:

Red:

Red: Module is Off-Line and no data exchange is possible.

Turned Off:

Turned Off:

Turned Off:

Turned Off: Module is not Off-Line.

4

Red

Bus diagnostics, indicates certain faults on the bus side.

Flashing Red 1 Hz:

Flashing Red 1 Hz:

Flashing Red 1 Hz:

Flashing Red 1 Hz: Error in configuration: IN and/or OUT length

set during initialisation of the module is not equal to the length

set during configuration of the network.

Flashing Red 2 Hz:

Flashing Red 2 Hz:

Flashing Red 2 Hz:

Flashing Red 2 Hz: Error in User Parameter data: The

length/contents of the User Parameter data set during

initialisation of the module is not equal to the length/contents set

during configuration of the network.

Flashing Red 4 Hz:

Flashing Red 4 Hz:

Flashing Red 4 Hz:

Flashing Red 4 Hz: Error in initialisation of the Profibus

communication ASIC.

Turned Off:

Turned Off:

Turned Off:

Turned Off: No diagnostics present

.book Page 54 Tuesday, January 19, 2010 1:07 PM