beautypg.com

Profibus dp, 4 technical data – KROHNE FC 300 Converter PROFIBUS PA-DP User Manual

Page 9

background image

PROFIBUS DP

2

9

IFC 300

www.krohne.com

02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en

2.4 Technical data

Hardware

Type

PROFIBUS RS485 interface according to IEC 61158-2

Connection

Dependent of polarity; please note at electrical connection!

Software

GSD

GSD file on CD-ROM or from internet site

Device profile

PA Profile compact class B, V 3.0

Address range

0…126 (default 126)

0…125 via PROFIBUS service set_slave_add

0…126 via local display

126 via factory_reset = 2712

Local control

Local display and operator interface at device

SAPs

2 x MS1 SAPs – acyclic interface to PLC

3 x MS2 SAPs – the number of MS2 Service Access Points is typically

equal to the maximum number of master class 2 tools

Function blocks

1 x TB = Transducer Block: contains the parameters and functions

defined in PA Profile 3.0

1 x PB = Physical Block: contains the parameters defined in PA

Profile 3.0

5 x AI = Analog Input Blocks: contains the parameters defined in PA

Profile 3.0

3 x TOT = Totalizer Function Blocks: contains the parameters defined

in PA Profile 3.0