Profibus dp, 4 technical data – KROHNE FC 300 Converter PROFIBUS PA-DP User Manual
Page 9
PROFIBUS DP
2
9
IFC 300
www.krohne.com
02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
2.4 Technical data
Hardware
Type
PROFIBUS RS485 interface according to IEC 61158-2
Connection
Dependent of polarity; please note at electrical connection!
Software
GSD
GSD file on CD-ROM or from internet site
Device profile
PA Profile compact class B, V 3.0
Address range
0…126 (default 126)
0…125 via PROFIBUS service set_slave_add
0…126 via local display
126 via factory_reset = 2712
Local control
Local display and operator interface at device
SAPs
2 x MS1 SAPs – acyclic interface to PLC
3 x MS2 SAPs – the number of MS2 Service Access Points is typically
equal to the maximum number of master class 2 tools
Function blocks
1 x TB = Transducer Block: contains the parameters and functions
defined in PA Profile 3.0
1 x PB = Physical Block: contains the parameters defined in PA
Profile 3.0
5 x AI = Analog Input Blocks: contains the parameters defined in PA
Profile 3.0
3 x TOT = Totalizer Function Blocks: contains the parameters defined
in PA Profile 3.0