Both, the Byte SetTot and ModeTot are cyclically sent from the Master to the device if these bytes
are inserted as output data via the PLC configurator. The meaning of these control bytes are as
follows:

Function of control bytes

All other values of ModeTot not allowed. Value is ignored; totalizer remains in its last valid
setting.

The standard block configuration may be changed by the customer but using the default settings
is highly recommended. If the standard block configuration should be changed by the customer
an acyclic master tool or the device display menu must be used to change the "channel
parameter" value of the block which should be connected to another transducer output value.

3.5.4 Profile specific GSD file: PA139740.GSD

The functionality of the profile specific GSD file is limited. This GSD file includes only two blocks:

The device has to be switched from full functionality to interchangeable basic configuration by
using one of both a master class 2 tool (IDENT_NUMBER_SELECTOR: Slot 0, Index 40; change
byte value to 0) or the device display menu. In the next step, the device has to be configured using
the PA039740.GSD file.

SetTot

SetTot

SetTot

SetTot

SetTot = 0

Totalizer is totalizing.

SetTot = 1

Totalizer will be reset to 0 and stays at 0 until SetTot is switched back

again to 0. If the value of SetTot changes from "1" to "0" the totalizer

starts counting from 0.

SetTot = 2

Totalizer is set to the value defined by PresetTot. PresetTot can be

written via an acyclic master (totalizer in block 2 = Slot 2 Index 32;

totalizer in block 3 = Slot 3 Index 32; totalizer in block 4 = Slot 4 Index

32). If the value of SetTot changes from "2" to "0" the totalizer starts

counting from the current value defined by PresetTot.

SetTot > 2

Not allowed. Value is ignored; totalizer remains in its last valid

setting.

ModeTot

ModeTot

ModeTot

ModeTot

ModeTot = 0

Totalizer totalizes positive and negative values.

ModeTot = 1

Totalizes only positive values.

ModeTot = 2

Totalizes only negative values.

ModeTot = 3

Totalizer is stopped, no totalization will be done.

ModeTot = 248

Totalizes all values as positive, negative values will be multiplied with

-1.0.

ModeTot = 249

Totalizes all values as negative, positive values will be multiplied with

-1.0.

Block
number

Standard configuration
Function block output value

PA139740.GSD
Ident-No. 9740

Default
unit

1

Volume Flow

AI-FB

m

3

/h

2

Volume Totalizer

Totalizer-FB

m

3