Profibus settings, 1 menu a, quick setup 5.2 menu b, test – KROHNE FC 300 Converter PROFIBUS PA-DP User Manual
Page 34
5
PROFIBUS SETTINGS
34
IFC 300
www.krohne.com
02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
For a detailed description of the menus and functions refer to the standard product
documentation of the signal converter. Some special settings concerning the PROFIBUS
features are easily operated via the local display menu (refer to the following sections).
5.1 Menu A, quick setup
5.2 Menu B, test
No.
Function
Settings / descriptions
A2 Tag
A2
Tag
Tag descriptor of the physical block of the PROFIBUS module will be
displayed. The Tag descriptor provides an application specific reference to
the blocks. It will be assigned by the user of the device. The Tag descriptor is
an octet string (a visible string will be preferred) consisting of 32 byte. The
first 21 characters will be displayed only!
A3 reset
A3
reset
-
A3.1
reset errors
This menu function can be used to reset all errors that are not removed
automatically (power fail, totalizer overflow)
reset? Select: no / yes
no: Exit the function.
yes: Resets the errors and exits the function.
The following reset menus for the totalizer are only available, if the quick access has been activated in the menu "setup
> device > quick setup". Each totalizer can be activated for quick access independently.
A3.2
FB2 totalizer 1
For PROFIBUS devices: The totalizer can be reset to zero in this menu.
A3.3
FB3 totalizer 2
A3.4
FB4 totalizer 3
A4 station address
A4
station address
Selects the address of the device at the PROFIBUS interface.
The PROFIBUS address can also be changed using the PROFIBUS service
"set_slave_add". The input range is 0...125 according to the PROFIBUS
specification. Address 126 is the default address and cannot be set via the
PROFIBUS service "set_slave_add" - use menu instead to reset to default
address.
No.
Function
Settings / descriptions
B3 information
B3.5
PROFIBUS
Available if there is a PROFIBUS interface in existence; displays the
following mentioned information about the PROFIBUS interface:
Ident No. / software revision no. of the PROFIBUS software / production date