5

PROFIBUS SETTINGS

34

IFC 300

www.krohne.com

02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en

For a detailed description of the menus and functions refer to the standard product
documentation of the signal converter. Some special settings concerning the PROFIBUS
features are easily operated via the local display menu (refer to the following sections).

5.1 Menu A, quick setup

5.2 Menu B, test

No.

Function

Settings / descriptions

A2 Tag

A2

Tag

Tag descriptor of the physical block of the PROFIBUS module will be

displayed. The Tag descriptor provides an application specific reference to

the blocks. It will be assigned by the user of the device. The Tag descriptor is

an octet string (a visible string will be preferred) consisting of 32 byte. The

first 21 characters will be displayed only!

A3 reset

A3

reset

-

A3.1

reset errors

This menu function can be used to reset all errors that are not removed

automatically (power fail, totalizer overflow)

reset? Select: no / yes

no: Exit the function.

yes: Resets the errors and exits the function.

The following reset menus for the totalizer are only available, if the quick access has been activated in the menu "setup

> device > quick setup". Each totalizer can be activated for quick access independently.

A3.2

FB2 totalizer 1

For PROFIBUS devices: The totalizer can be reset to zero in this menu.

A3.3

FB3 totalizer 2

A3.4

FB4 totalizer 3

A4 station address

A4

station address

Selects the address of the device at the PROFIBUS interface.

The PROFIBUS address can also be changed using the PROFIBUS service

"set_slave_add". The input range is 0...125 according to the PROFIBUS

specification. Address 126 is the default address and cannot be set via the

PROFIBUS service "set_slave_add" - use menu instead to reset to default

address.

No.

Function

Settings / descriptions

B3 information

B3.5

PROFIBUS

Available if there is a PROFIBUS interface in existence; displays the

following mentioned information about the PROFIBUS interface:

Ident No. / software revision no. of the PROFIBUS software / production date