Profibus settings – KROHNE FC 300 Converter PROFIBUS PA-DP User Manual
Page 36
5
PROFIBUS SETTINGS
36
IFC 300
www.krohne.com
02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
C4. .3
error behaviour
Defines the behaviour of this function block in case of errors.
Select: hold value / ignore error / replace value
hold value:
hold value:
hold value:
hold value: Last valid OUT value stored will be used as OUT value.
ignore error:
ignore error:
ignore error:
ignore error: OUT has the wrong calculated value and status "Bad" as
calculated.
replace value:
replace value:
replace value:
replace value: The "replacement value" will be used as OUT value.
C4. .4
replacement value
Available, if the error behaviour "replace value" is selected. Defines the
value that replaces the measured value at this function block in case of an
error.
C5 device
C5.1.1
Tag
Tag descriptor of the physical block of the PROFIBUS module will be
displayed. The Tag descriptor provides an application specific reference to
the blocks. It will be assigned by the user of the device. The Tag descriptor is
an octet string (a visible string will be preferred) consisting of 32 byte. The
first 21 characters will be displayed only!
C5.3
1. meas. page
Setting of the measurement for the 1st measuring page.
C5.3.2
measurement 1.line
Specify measurement for 1st line.
Select: volume flow / mass flow (not
not
not
not valid for PF (partly filled)) / diagnosis
value / flow speed / coil temperature / conductivity (not
not
not
not valid for PF (partly
filled)) and CAP (capacitive)) / level (only
only
only
only valid for PF (partly filled))
C5.3.8
measurement 2.line
Specify measurement of 2nd line (only available if this 2.line is activated)
Select: bar graph (for the measurement selected in the first line) / volume
flow / mass flow (not
not
not
not valid for PF (partly filled)) / diagnosis value / flow
speed / FB2 totalizer 1 / FB3 totalizer 2 / FB4 totalizer 3 / conductivity (not
not
not
not
valid for PF (partly filled) and CAP (capacitive)) / coil temperature / operating
hours / level (only
only
only
only valid for PF (partly filled))
C5.3.10
measurement 3.line
Specify measurement of 3rd line (only available if this 3.line is activated)
Select: volume flow / mass flow (not
not
not
not valid for PF (partly filled)) / diagnosis
value / flow speed / coil temperature / conductivity (not
not
not
not valid for PF (partly
filled) and CAP (capacitive)) / FB2 totalizer 1 / FB3 totalizer 2 /
FB4 totalizer 3 / operating hours / level (only
only
only
only valid for PF (partly filled)) /
current input A / current input B
C5.4
2. meas. page
Setting of the measurement for the second measuring page.
For PROFIBUS devices this page shows only the PROFIBUS values
FB1…FB8.
C5.4.1
C5.4.3
C5.4.5
measurement 1.line
measurement 2.line
measurement 3.line
Select the measurement of the 1st, 2nd and 3rd line:
FB1 analog inp. / FB2 totalizer 1 / FB3 totalizer 2 / FB4 totalizer 3 / FB6
analog inp. / FB7 analog inp. / FB8 analog inp.
C5.4.2
C5.4.4
C5.4.6
format 1.line
format 2.line
format 3.line
Fixed number of digits after the decimal point or automatic, where the
number of digits is automatically adjusted to the available space.
C5.6
special functions
-
C5.6.1
reset errors
This menu function can be used to reset all errors that are not removed
automatically (power fail, totalizer overflow)
reset? Select: no / yes
C5.6.2
save settings
Save current settings.
Select: break (exit function without saving) / backup 1 (save in storage
location 1) / backup 2 (save in storage location 2)
Query: continue copy? (cannot be undone)
Select: no (exit function without saving) / yes (copy current settings to
storage backup 1 or backup 2)
No.
Function
Settings / descriptions