Definition of totalizer functions
Both, the Byte SetTot and ModeTot are cyclically sent from the master to the device if these bytes
are inserted as output data via the PLC configurator. The meaning of these control bytes are as
follows:
Function of control bytes
All other values of ModeTot not allowed. Value is ignored; totalizer remains in its last valid
setting.
The standard block configuration may be changed by the customer but using the default settings
is highly recommended. If the standard block configuration should be changed by the customer
an acyclic master tool or the device display menu must be used to change the "channel
parameter" value of the block which should be connected to another transducer output value.
Total
cyclic transfer of the totalizer value with status to the master
SetTot + Total
cyclic transfer of the totalizer value with status to the master + cyclic
control data from master to the device via the parameter SetTot
ModeTot + Total
cyclic transfer of the totalizer value with status to the master + cyclic
control data from master to the device via the parameter ModeTot
SetTot + ModeTot + Total
cyclic transfer of the totalizer value with status to the master + cyclic
control data from master to the device via the parameters SetTot and
ModeTot (in the given order)
SetTot
cyclic control data from master to the device via the parameter
SetTot
ModeTot
cyclic control data from master to the device via the parameter
ModeTot
SetTot + ModeTot
cyclic control data from master to the device via the parameters
SetTot and ModeTot (in the given order)
SetTot
SetTot
SetTot
SetTot
SetTot = 0
Totalizer is totalizing.
SetTot = 1
Totalizer will be reset to 0 and stays at 0 until SetTot is switched back
again to 0. If the value of SetTot changes from "1" to "0" the totalizer
starts counting from 0.
SetTot = 2
Totalizer is set to the value defined by PresetTot. PresetTot can be
written via an acyclic master (totalizer in block 2 = Slot 2 Index 32;
totalizer in block 3 = Slot 3 Index 32; totalizer in block 4 = Slot 4 Index
32). If the value of SetTot changes from "2" to "0" the totalizer starts
counting from the current value defined by PresetTot.
SetTot > 2
Not allowed. Value is ignored; totalizer remains in its last valid
setting.
ModeTot
ModeTot
ModeTot
ModeTot
ModeTot = 0
Totalizer totalizes positive and negative values.
ModeTot = 1
Totalizes only positive values.
ModeTot = 2
Totalizes only negative values.
ModeTot = 3
Totalizer is stopped, no totalization will be done.
ModeTot = 248
Totalizes all values as positive, negative values will be multiplied with
-1.0.
ModeTot = 249
Totalizes all values as negative, positive values will be multiplied with
-1.0.