PROFIBUS PA

3

21

IFC 300

www.krohne.com

02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en

Definition of totalizer functions

INFORMATION!
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. This is performed by a bus
configuration tool (e.g. "HW- Config" for PC-S7 from Siemens). This tool offers specific functions
as follows:
1. It is possible to configure an "Empty" block (the code of an "Empty" block is defined as 0x00) on

each block number. This implies: no data are transmitted in the cyclic data telegram for this
block.

2. There is NO "Totalizer (TOT)" function block allowed on block position 1, 5, 6, 7 and 8! On these

positions, only an "Analog Input (AI)" function block or an "Empty" block is allowed!
(Note: All codes supported by "Analog Input (AI)" - and "Totalizer (TOT)"

function blocks will

be found in the corresponding GSD files.)

3. There is NO "Analog Input (AI)" function block allowed on block position 2, 3 and 4! On these

positions, only a "Totalizer (TOT)" function block or an "Empty" block is allowed!

4. There is a choice of 7 different totalizer functions, which can be allocated to the blocks 2, 3

and/or 4.

Total

cyclic transfer of the totalizer value with status to the master

SetTot + Total

cyclic transfer of the totalizer value with status to the master + cyclic

control data from master to the device via the parameter SetTot

ModeTot + Total

cyclic transfer of the totalizer value with status to the master + cyclic

control data from master to the device via the parameter ModeTot

SetTot + ModeTot + Total

cyclic transfer of the totalizer value with status to the master + cyclic

control data from master to the device via the parameters SetTot and

ModeTot (in the given order)

SetTot

cyclic control data from master to the device via the parameter

SetTot

ModeTot

cyclic control data from master to the device via the parameter

ModeTot

SetTot + ModeTot

cyclic control data from master to the device via the parameters

SetTot and ModeTot (in the given order)