APPLICATION PROFILE
28
IFC 300
www.krohne.com
02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
4.3 Diagnosis parameter
4.3.1 Diagnosis
Parameter DIAGNOSIS will contain detailed information of the device, bitwise coded. More than
one message possible at once (as below-mentioned). If MSB of byte 4 is set to 1 than more
diagnose information is available in the DIAGNOSIS_EXTENSION parameter.
The manufacturer specific parameter "DIAGNOSIS_EXTENSION" will contain bitwise coded
more detailed information of the internal status conditions and error conditions of the
PROFIBUS device.
The corresponding GSD file will contain all messages supported by this device - have a look at
the UNIT_DIAG_BIT(i) definitions.
4.3.2 DIAGNOSIS (if "Classic Status" and "Diagnosis" selected)
Octet number
Bit number
Subparam
eter
Indication type
De
fault value
De
script
ion
1
0
DIA_HW_ELECTR
0
Hardware failure electronics
1
DIA_HW_MECH
0
Hardware failure mechanics
2
DIA_TEMP_MOTOR
0
Motor temperature too high
3
DIA_TEMP_ELECTR
0
Electronic temperature too high
4
DIA_MEM_CHKSUM
0
Memory error
5
DIA_MEASUREMENT
0
Measurement failure
6
DIA_NOT_INIT
0
Device not initialized
7
DIA_INIT_ERR
0
Device initialization failed
2
0
DIA_ZERO_ERR
0
Zero point error
1
DIA_SUPPLY
0
Power supply failed
2
DIA_CONF_INVAL
0
Configuration invalid
3
DIA_WARMSTART
A
0
Restart (warmstart)
4
DIA_COLDSTART
A
0
Coldstart (with default data)
5
DIA_MAINTENANCE
R
0
Maintenance required
6
DIA_CHARACT
R
0
Characteristics invalid
7
IDENT_NUMBER_VIOLATION
R
0
Ident. No. violation:
Set to 1 if the Ident_Number of the running cyclic
data transfer and the value of physical block
IDENT_NUMBER_SELECTOR parameter are
different