PROFIBUS DP
2
13
IFC 300
www.krohne.com
02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
2.5.5 Differencies of the manufacturer specific GSD files: KR024500.GSD and
KR014500.GSD
2.5.6 Profile specific GSD file: PA039740.GSD
The functionality of the profile specific GSD file is limited. This GSD file includes only two blocks:
The device has to be switched from full functionality (manufacturer specific) to interchangeable
basic configuration (profile specific) by using both a master class 2 tool or the device display
menu (IDENT_NUMBER_SELECTOR: Slot 0, Index 40; change byte value to 0). In the next step,
the device has to be configured using the PA039740.GSD file.
2.5.7 Using the display menu to distinguish between Rev 1 and Rev 2
Rev 1 [= = DP signal converter (RS485) Rev 1] and Rev 2 [= = DP signal converter (RS485) Rev 2]
Use the display to open the Fct. 3.5 of the signal converter (if not available, see below Rev 1). You
will get the following information:
• KROHNE Ident.-No. (of the assembled PROFIBUS PCB)
• Software revision (of the PROFIBUS software)
• Date of production (of the PROFIBUS device)
Your device is Rev 1, if
• the Fct. No. mentioned above is not available
• the indicated software revision number is = 1.0.x
Your device is Rev 2, if
• the indicated software revision number is = 1.1.x
• the indicated software revision number is ≥ 2.0
KR024500.GSD
(includes the complete functionality)
KR014500.GSD
(functions are only partially supported)
GSD Revision 5.02
GSD Revision 3
PROFIBUS-PA Profile 3.0x and I&M
PROFIBUS PA Profile 3.0x
Ident_Maintenance_supp = 1 (== supported)
-
Fail_Safe (Extended DP-Features)
-
C2_Max_Data_Len = 132
C2_Max_Data_Len = 128
Max_Initiate_PDU_Length = 132
Max_Initiate_PDU_Length = 128
Unit_Diag_Bit(82) = "DP - measurement not
available"
Unit_Diag_Bit(83) = "DP - power fail"
Unit_Diag_Bit(82) = "reserved (82)"
Unit_Diag_Bit(83) = "reserved (83)"
Block
number
Standard configuration
Function block output value
PA039740.GSD
Ident-No. 9740
Default
unit
1
Volume Flow
AI-FB
m
3
/h
2
Volume Totalizer
Totalizer-FB
m
3