PROFIBUS SETTINGS
5
37
IFC 300
www.krohne.com
02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
C5.6.3
load settings
Load saved settings.
Select: break (exit function without loading) / factory settings (load in state
as delivered) / backup 1 (load data from storage location 1) / backup 2 (load
data from storage location 2) / load sensor data (factory settings of
calibration data)
Query: continue copy? (cannot be undone)
Select: no (exit the function without saving) / yes (load data from the selected
storage location)
C5.8
physical block
This menu is only available, if a PROFIBUS interface is present.
C5.8.1
station address
Selects the PROFIBUS station address of the device.
The PROFIBUS address can also be changed using the PROFIBUS service
"set_slave_add". The input range is 0...125 according to the PROFIBUS
specification. Address 126 is the default address and cannot be set via the
PROFIBUS service "set_slave_add" - use menu instead to reset to default
address.
C5.8.2
information
Available if there is a PROFIBUS interface in existence; displays the
following mentioned information about the PROFIBUS interface:
Ident No. / software revision no. of the PROFIBUS software / production date
C5.8.3
diag. extension
Content of the PROFIBUS diagnosis extension is displayed.
C5.8.4
diag. extension 2
Content of the additional, internal diagnosis stored is displayed.
C5.8.6
diag. extension h
h = history
Content of the PROFIBUS diagnosis extension is displayed.
Shows diagnosis information of all diagnosis bits, which are set again since
the last delete.
C5.9
quick setup
Activate quick access in quick setup menu; default setting: quick setup is
active (yes)
Select: yes (switched on) / no (switched off)
C5.9.1
reset totalizer 1
The reset can be activated in the "quick setup" to get a quick access of the
function.
Select: yes (activated) / no (switched off)
C5.9.2
reset totalizer 2
C5.9.3
reset totalizer 3
No.
Function
Settings / descriptions