Profibus pa – KROHNE FC 300 Converter PROFIBUS PA-DP User Manual

Page 20

background image

3

PROFIBUS PA

20

IFC 300

www.krohne.com

02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en

3.5.3 Manufacturer specific GSD files: KR024501.GSD and YP024501.GSD

The KR024501.GSD file is for use with the standard DP/PA coupler and the YP024501.GSD file is
for use with the transparent DP/PA coupler SK2/SK3 of Pepperl & Fuchs (up to 12 MBaud on the
DP segment).

It should be noted that both GSD files support device functionality as described below:

• AI: Analog Input Function Block
• FB: Function Block
• X: Block number 1, 5, 6, 7 or 8

There will be two additional output values available by changing the function block channel
parameters of the above mentioned "Analog Input Function Blocks".

There are separate settings to select the units for local display and PROFIBUS. Modifications of
the units of the display will have no effect on the data transferred via PROFIBUS. A master class
2 tool is required to modify the units for PROFIBUS transfer.

INFORMATION!
For devices with MBP interface there are always two types of GSD files in our GSD compilation:

One standard GSD file for a standard DP/PA segment coupler with file name: "KR0

.GSD"

One special GSD file specific for the segment coupler SK2/SK3 of Pepperl & Fuchs with file
name: "YP0

.GSD"

Block
number

Default configuration
Function block output: value and
status

KR024501.GSD
YP024501.GSD
Ident-No. 4501

Default
unit

1

Volume Flow

AI-FB

m

3

/h

2

Volume Totalizer

Totalizer-FB

m

3

3

Volume Totalizer

Totalizer-FB

m

3

4

Mass Totalizer

Totalizer-FB

kg

5

Mass Flow

AI-FB

kg/s

6

Speed Flow

AI-FB

m/s

7

Coil Temperature

AI-FB

K

8

Conductivity

AI-FB

S/m

X

Electronic Temperature

AI-FB

°

C

X

Supply

(internal supply voltage for the

PROFIBUS interface)

AI-FB

V