Profibus settings, 4 menu d, service – KROHNE FC 300 Converter PROFIBUS PA-DP User Manual
Page 38
5
PROFIBUS SETTINGS
38
IFC 300
www.krohne.com
02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
5.4 Menu D, service
This menu is protected. You will need to use the service password to gain access.
No.
Function
Settings / descriptions
D2
service parameters
In this menu all functions related to different data sets can be found.
D2.1
cold start
Resetting of the signal converter can be done here but all changes up to this
point are automatically stored and cannot be discarded.
Select: no (terminates the function) / yes (performs the reset and leaves the
setting mode)
D2.2
save factory data
Copies the actual data into the factory setting; this overwrites the factory
settings done during calibration!
Query: save settings? (cannot be undone)
Select: break (exit function without saving) / factory settings (saves the
settings as factory settings)
Query: continue copy? (cannot be undone)
Select: no (exit function without saving) / yes (copy current settings to the
selected storage location)
D2.9
Identification No.
Sets different device modes for the cyclic communication of the PROFIBUS
interface.
Select: signal converter (the normal settings incl. all manufacturer specific
parameters are supported) / profile (uses only the profile defined functions,
no extras, only profile specific parameters are supported) / IFC090
(compatibility mode)
D2.10
PB cold start
Initiates a PROFIBUS cold start.
During a PROFIBUS cold start nearly all parameter values of the whole
device will be set to their default values (Exceptions are the PROFIBUS
address and the identification No.). The cold start will be carried out without
disconnecting an already established connection to a PROFIBUS master
system.
Query: reset? (to default values) = cold start begins
Select: no (terminates the function) / yes (PROFIBUS cold start will be
carried out at once; the setting mode is terminated)
D2.12
diag. extension h
h = history
Delete the stored history.
Query: reset? = reset history to 0)
Select: no (no change) / yes (all saved data are deleted)