3.4 Cable types

The cable types are specified according to IEC 61158-2. Shielded cables offer the advantage of
malfunction-free operation with adequate protection against electromagnetic influences, and
make it possible to employ the full performance of the Foundation Fieldbus system.

In non-hazardous areas the maximum number of field devices is limited to 32. For detailed
information refer to the following table.

In non-hazardous areas the ignition protection class of the devices and the limited electric power
available limit the number of field devices to 4.

All bus segments must be fitted with a terminator at both ends.

3.5 Shielding and grounding

• For optimum electromagnetic compatibility of systems it is extremely important that the

system components, and particularly the bus cables connecting the components, are
shielded and that such shields - if possible - form an unbroken cover.

• Hence, it follows that, for use in non-hazardous duty systems, the cable shield should be

grounded as often as possible.

• In Ex systems an adequate equipotential bonding in the hazardous and non-hazardous

location along the entire Fieldbus installation is strongly recommended. Multiple grounding
of the shield is of advantage.

Core cross-section

0.8 mm

2

or

AWG 18

0.32 mm

2

or

AWG 22

0.13 mm

2

or

AWG 26

1.25 mm

2

or

AWG 16

Cable type

A

A

A

A

B

B

B

B

C

C

C

C

D

D

D

D

twisted pair,

individually

shielded

individual or

multiple twisted

pairs with overall

shield

multiple twisted

pairs, without

shielding

multiple non-

twisted cables,

without shielding

Max. length

incl. branch line

1900 m / 6200 ft

1200 m / 3900 ft

400 m / 1300 ft

200 m / 650 ft

Number of devices

Cable lengths for number of devices per branch line

1 device

2 devices

3 devices

4 devices

25...32

1 m / 3.3 ft

1 m / 3.3 ft

1 m / 3.3 ft

1 m / 3.3 ft

19...24

30 m / 100 ft

1 m / 3.3 ft

1 m / 3.3 ft

1 m / 3.3 ft

15...18

60 m / 200 ft

30 m / 100 ft

1 m / 3.3 ft

1 m / 3.3 ft

13...14

90 m / 300 ft

60 m / 200 ft

30 m / 100 ft

1 m / 3.3 ft

1..12

120 m / 400 ft

90 m / 300 ft

60 m / 200 ft

30 m / 100 ft

INFORMATION!
The use of twisted and shielded cables is strongly recommended, otherwise EMC protection of
the signal converter cannot be assured.