beautypg.com

Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual

Page 14

background image

4

OPERATION

14

IFC 100

www.krohne.com

02/2012 - 4001702901 - AD IFC 100 FF R01 en

DEV_REV

DEV_REV

DEV_REV

DEV_REV

Device Revision

Device Revision

Device Revision

Device Revision

R

Manufacturer revision number associated with the resource -

used by an interface device to locate the DD file for the

resource.

Dependent on

device version

Setting:

Dependent on device version

DEV_TYPE

DEV_TYPE

DEV_TYPE

DEV_TYPE

Device Type

Device Type

Device Type

Device Type

R

Manufacturer's model number associated with the resource -

used by interface devices to locate the DD file for the

resource.

IFC100

Setting:

IFC100

FAULT_STATE

FAULT_STATE

FAULT_STATE

FAULT_STATE

Fault State

Fault State

Fault State

Fault State

R

Condition set by loss of communication to an output block,

failure promoted to an output block or a physical contact.

When fault state condition is set, then output function blocks

will perform their "FSTATE" actions.

Clear

Setting:

Uninitialized / Clear / Active

FEATURES

FEATURES

FEATURES

FEATURES

Features

Features

Features

Features

R

Used to shows supported resource block options.

Reports /

Soft W Lock /

MVC Report

Distribution

supported /

MVC

Publishing/Subscri

bing supported/

Multi-bit Alarm

(Bit-Alarm)

Support

Setting:

Reports / Soft W Lock / MVC Report Distribution supported /

MVC Publishing/Subscribing supported / Multi-bit Alarm (Bit-

Alarm) Support

FEATURES_SEL

FEATURES_SEL

FEATURES_SEL

FEATURES_SEL

Features Selection

Features Selection

Features Selection

Features Selection

R/W

Used to select resource block options.

Reports /

Soft W Lock

Setting:

Reports / Soft W Lock / MVC Report Distribution supported /

MVC Publishing/Subscribing supported / Multi-bit Alarm (Bit-

Alarm) Support

FREE_SPACE

FREE_SPACE

FREE_SPACE

FREE_SPACE

Free Space

Free Space

Free Space

Free Space

R

Percent of the memory available for further configuration.

Zero in a preconfigured device.

0.0

Setting:

0.0…100.0

FREE_TIME

FREE_TIME

FREE_TIME

FREE_TIME

Free Time

Free Time

Free Time

Free Time

R

Percent of the block processing time that is free to process

additional blocks.

0.0

Setting:

0.0…100.0

GRANT_DENY

GRANT_DENY

GRANT_DENY

GRANT_DENY

Grant Deny

Grant Deny

Grant Deny

Grant Deny

Options for controlling access of host computers and local

control panels to operating, tuning and alarm parameters of

the block.

-

GRANT

Grant

R/W

Depending on the philosophy of the plant, the operator or a

higher level device (HLD) or a local operator's panel (LOP) in

the case of "Local", may turn on an item of the "Grant"

attribute - "Program, Tune, Alarm or Local".

Uninitialized

Setting:

Program / Tune / Alarm / Local / Operate

DENY

Deny

R/W

The denied attribute is limited for use by a monitoring

application in an interface device and may not be changed by

an operator.

Uninitialized

Setting:

Program denied / Tune denied / Alarm denied / Local denied /

Operate denied

HARD_TYPES

HARD_TYPES

HARD_TYPES

HARD_TYPES

Hard Types

Hard Types

Hard Types

Hard Types

R

The types of hardware available as channel numbers.

Scalar input

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value

This manual is related to the following products: