Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual

Page 36

background image

4

OPERATION

36

IFC 100

www.krohne.com

02/2012 - 4001702901 - AD IFC 100 FF R01 en

HI_PRI

HI_PRI

HI_PRI

HI_PRI

High Priority

High Priority

High Priority

High Priority

R/W

Priority of the "High Alarm".

0

Setting:

0...15

IO_OPTS

IO_OPTS

IO_OPTS

IO_OPTS

IO Options

IO Options

IO Options

IO Options

(IO = Input/Output)

(IO = Input/Output)

(IO = Input/Output)

(IO = Input/Output)

R/W

Options which the user may select to alter input and output

block processing.

Uninitialized

Settings:

Low Cutoff / Units Conversion

L_TYPE

L_TYPE

L_TYPE

L_TYPE

Linearization Type

Linearization Type

Linearization Type

Linearization Type

R/W

Determines if the values passed by the TB to the AI block may

be used directly (Direct) or if the value is in different units and

must be converted linearly (Indirect) or with square root (Ind

Sqr Root), using the input range defined by the transducer and

the associated output range.

Uninitialized

Setting:

Uninitialized / Direct / Indirect / Ind Sqr Root

LO_ALM

LO_ALM

LO_ALM

LO_ALM

Low Alarm

Low Alarm

Low Alarm

Low Alarm

The status for "Low Alarm" and its associated time stamp.

Settings of 5 subelements see in the following part.

-

LO_LO_ALM

LO_LO_ALM

LO_LO_ALM

LO_LO_ALM

Low Low Alarm

Low Low Alarm

Low Low Alarm

Low Low Alarm

Mix

The status for "Low Low Alarm" and its associated time

stamp.

Settings of 5 subelements see in the following part.

-

Settings of 5 subelements for previous 2 parameters "Low Alarm" and "Low Low Alarm":

UNACKNOWLEDGED

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

ALARM_STATE

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

SUB_CODE

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

Other

Setting:

Other / Block Configuration / Link Configuration / Simulation

Active / Local Override / Device Fault State / Device

Maintenance / Input Failure / Output Failure / Memory

Failure / Lost Static Data / Lost NV Data / Readback Check /

Maintenance Needed / Power Up / Out Of Service

VALUE

Float value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

LO_LIM

LO_LIM

LO_LIM

LO_LIM

Low Limit

Low Limit

Low Limit

Low Limit

R/W

The setting for "Low Alarm" in engineering units.

(-NaN)

Setting:

-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)

LO_LO_LIM

LO_LO_LIM

LO_LO_LIM

LO_LO_LIM

Low Low Limit

Low Low Limit

Low Low Limit

Low Low Limit

R/W

The setting for "Low Low Alarm" in engineering units.

(-NaN)

Setting:

-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)