Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual
Page 59
OPERATION
4
59
IFC 100
www.krohne.com
02/2012 - 4001702901 - AD IFC 100 FF R01 en
STATUS_OPTS
STATUS_OPTS
STATUS_OPTS
STATUS_OPTS
Status Options
Status Options
Status Options
Status Options
R/W
Options which the user may select in the block processing of
status.
No option selected
Setting:
•
IFS if Bad IN: Set Initiate Fault State status in OUT if the
status of IN is "Bad".
•
IFS if Bad CAS_IN: Set Initiate Fault State status in OUT if the
status of CAS_IN is "Bad".
•
Use Uncertain as Good: If the status of IN is "Uncertain",
treat it as "Good" otherwise treat it as "Bad".
•
Target to Man if Bad IN: Set the target mode to "Man" if the
status of the IN parameter is "Bad". This latches a PID block
into the "Man" state of the input ever goes "Bad".
•
Target to next permitted mode if BAD CAS_IN
TRK_IN_D
TRK_IN_D
TRK_IN_D
TRK_IN_D
Tracking Input
Tracking Input
Tracking Input
Tracking Input
Discrete
Discrete
Discrete
Discrete
R/W
This discrete input is used to initiate external tracking of the
block output to the value specified by TRL_VAL.
-
Status
R/W
Status of TRK_IN_D
-
Value
R/W
Value of TRK_IN_D
-
TRK_SCALE
TRK_SCALE
TRK_SCALE
TRK_SCALE
Tracking Scale
Tracking Scale
Tracking Scale
Tracking Scale
R/W
The high and low scale values, engineering units code and
number of digits to the right of the decimal point associated
with TRK_VAL.
-
EU at 100%
R/W
The engineering unit value which represents the upper end of
range of the associated block parameter.
100
EU at 0%
R/W
The engineering unit value which represents the lower end of
range of the associated block parameter.
0
Units Index
R/W
Device Description units code index for the engineering unit
descriptor for the associated block value.
Uninitialized
Setting:
All units are possible.
Decimal Point
R/W
The number of digits to the right of the decimal point which
should be used by an interface device in displaying the
specified parameter.
0
TRK_VALUE
TRK_VALUE
TRK_VALUE
TRK_VALUE
Tracking Value
Tracking Value
Tracking Value
Tracking Value
R/W
This input is used as the track value when external tracking is
enabled by TRK_IN_D.
-
Status
R/W
Status of TRK_VAL
-
Value
R/W
Value of TRK_VAL
-
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
Update Event
Update Event
Update Event
Update Event
R
This alert is generated by any change to the static data.
-
Unacknowledged
R
A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Update State
R
A discrete enumeration which gives an indication of whether
the alert has been reported.
Uninitialized
Setting:
Uninitialized / Reported / Not Reported
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value