Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual

Page 38

background image

4

OPERATION

38

IFC 100

www.krohne.com

02/2012 - 4001702901 - AD IFC 100 FF R01 en

TRANSDUCER_

STATUS

Transducer Status

R

Status of value supplied by transducer.

0

TRANSDUCER_VALUE

Transducer Value

R

Current value supplied by transducer.

0.0

ENABLE_DISABLE

Simulate En/Disable

R/W

Enable/disable simulation.

Disabled

Setting:

Uninitialized / Disabled / Active

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

Status Option

Status Option

Status Option

Status Option

R/W

Options which the user may select in the block processing of

status.

Uninitialized

Setting:

Propagate Fault Fwd / Uncertain if Limited / BAD if Limited /

Uncertain if Man.

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

Update Event

Update Event

Update Event

Update Event

This alert is generated by any change to the static data.

-

UNACKNOWLEDGED

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

UPDATED_STATE

Updated State

R

A discrete enumeration which gives an indication of whether

the alert has been reported.

Uninitialized

Setting:

Uninitialized / Reported / Not Reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

-

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

STATIC_REVISION

Static Revision

R

The static revision of the block whose static parameter was

changed and is being reported. It is possible for the present

value of static revision to be greater than this because static

can be changed at any time.

0

RELATIVE_INDEX

Relative Index

R

The OD index of the static parameter whose change caused

this alert, minus the FB starting index. If the update event was

caused by a write to multiple parameters at the same time,

then this attribute will be zero.

0

XD_SCALE

XD_SCALE

XD_SCALE

XD_SCALE

Transducer Scale

Transducer Scale

Transducer Scale

Transducer Scale

The high and low scale values, engineering units code and

number of digits to the right of the decimal point used with the

value obtained from the transducer for a specified channel.

-

EU_100

EU at 100%

R/W

The engineering unit value which represents the upper end of

range of the associated block parameter.

100

EU_0

EU at 0%

R/W

The engineering unit value which represents the lower end of

range of the associated block parameter.

0