Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual
Page 38
4
OPERATION
38
IFC 100
www.krohne.com
02/2012 - 4001702901 - AD IFC 100 FF R01 en
TRANSDUCER_
STATUS
Transducer Status
R
Status of value supplied by transducer.
0
TRANSDUCER_VALUE
Transducer Value
R
Current value supplied by transducer.
0.0
ENABLE_DISABLE
Simulate En/Disable
R/W
Enable/disable simulation.
Disabled
Setting:
Uninitialized / Disabled / Active
STATUS_OPTS
STATUS_OPTS
STATUS_OPTS
STATUS_OPTS
Status Option
Status Option
Status Option
Status Option
R/W
Options which the user may select in the block processing of
status.
Uninitialized
Setting:
Propagate Fault Fwd / Uncertain if Limited / BAD if Limited /
Uncertain if Man.
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
Update Event
Update Event
Update Event
Update Event
This alert is generated by any change to the static data.
-
UNACKNOWLEDGED
Unacknowledged
R/W
A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
UPDATED_STATE
Updated State
R
A discrete enumeration which gives an indication of whether
the alert has been reported.
Uninitialized
Setting:
Uninitialized / Reported / Not Reported
TIME_STAMP
Time Stamp
R
The time when evaluation of the block was started and a
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received - even if another change of
state occurs.
-
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
STATIC_REVISION
Static Revision
R
The static revision of the block whose static parameter was
changed and is being reported. It is possible for the present
value of static revision to be greater than this because static
can be changed at any time.
0
RELATIVE_INDEX
Relative Index
R
The OD index of the static parameter whose change caused
this alert, minus the FB starting index. If the update event was
caused by a write to multiple parameters at the same time,
then this attribute will be zero.
0
XD_SCALE
XD_SCALE
XD_SCALE
XD_SCALE
Transducer Scale
Transducer Scale
Transducer Scale
Transducer Scale
The high and low scale values, engineering units code and
number of digits to the right of the decimal point used with the
value obtained from the transducer for a specified channel.
-
EU_100
EU at 100%
R/W
The engineering unit value which represents the upper end of
range of the associated block parameter.
100
EU_0
EU at 0%
R/W
The engineering unit value which represents the lower end of
range of the associated block parameter.
0