Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual

Page 20

background image

4

OPERATION

20

IFC 100

www.krohne.com

02/2012 - 4001702901 - AD IFC 100 FF R01 en

PID_DIAG

PID

R

Reason for OUT.status not good, bits at BLK_ERR and other

diagnosis.

Current diagnosis

Setting:

Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory

failure / no schedule / period of execution / period of

execution too large / MODE_BLK.PERMITTED doesn't include

Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is

set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /

BYPASS is uninitialized / SHED_OPT is uninitialized /

PV_SCALE : EU_100 <= EU_0 / OUT_SCALE : EU_100 <=

EU_0 / TRK_SCALE : EU_100 <= EU_0 / FF_SCALE : EU_100

<= EU_0 / unknown reason / ok

IT1/2_DIAG

IT1/2

R

Reason for OUT.status not good, bits at BLK_ERR and other

diagnosis .

Current diagnosis

Setting:

Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory

failure / no schedule / period of execution / period of

execution too large / MODE_BLK.PERMITTED doesn't include

Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is

set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /

INTEG_TYPE is uninitialized / IN_1 and IN_2 are not

connected / TIME_UNIT1 and TIME_UNIT2 are uninitialized /

CLOCK_PER <= period of execution / TIME_UNIT1 is

uninitialized / TIME_UNIT2 is uninitialized / IN_1.status is

Bad / IN_2.status is Bad / IN_1.value is NaN or INF /

IN_2.value is NaN or INF / PCT_INCL < UNCERT_LIM /

PCT_INCL < GOOD_LIM / PULSE_VAL1 and PULSE_VAL2 are

0 / TOTAL_SP is 0 : cyclic reset / unknown reason / ok