Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual
Page 20
4
OPERATION
20
IFC 100
www.krohne.com
02/2012 - 4001702901 - AD IFC 100 FF R01 en
PID_DIAG
PID
R
Reason for OUT.status not good, bits at BLK_ERR and other
diagnosis.
Current diagnosis
Setting:
Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution too large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
BYPASS is uninitialized / SHED_OPT is uninitialized /
PV_SCALE : EU_100 <= EU_0 / OUT_SCALE : EU_100 <=
EU_0 / TRK_SCALE : EU_100 <= EU_0 / FF_SCALE : EU_100
<= EU_0 / unknown reason / ok
IT1/2_DIAG
IT1/2
R
Reason for OUT.status not good, bits at BLK_ERR and other
diagnosis .
Current diagnosis
Setting:
Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution too large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
INTEG_TYPE is uninitialized / IN_1 and IN_2 are not
connected / TIME_UNIT1 and TIME_UNIT2 are uninitialized /
CLOCK_PER <= period of execution / TIME_UNIT1 is
uninitialized / TIME_UNIT2 is uninitialized / IN_1.status is
Bad / IN_2.status is Bad / IN_1.value is NaN or INF /
IN_2.value is NaN or INF / PCT_INCL < UNCERT_LIM /
PCT_INCL < GOOD_LIM / PULSE_VAL1 and PULSE_VAL2 are
0 / TOTAL_SP is 0 : cyclic reset / unknown reason / ok