OPERATION

4

35

IFC 100

www.krohne.com

02/2012 - 4001702901 - AD IFC 100 FF R01 en

GRANT_DENY

GRANT_DENY

GRANT_DENY

GRANT_DENY

Grant Deny

Grant Deny

Grant Deny

Grant Deny

Options for controlling access of host computers and local

control panels to operating, tuning and alarm parameters of

the block.

-

GRANT

Grant

R/W

Depending on the philosophy of the plant, the operator or a

higher level device (HLD) or a local operator's panel (LOP) in

the case of "Local", may turn on an item of the "Grant"

attribute - "Program, Tune, Alarm or Local".

Uninitialized

Setting:

Program / Tune / Alarm / Local / Operate

DENY

Deny

R/W

The denied attribute is provided for use by a monitoring

application in an interface device and may not be changed by

an operator.

Uninitialized

Setting:

Program denied / Tune denied / Alarm denied / Local denied /

Operate denied

HI_ALM

HI_ALM

HI_ALM

HI_ALM

High Alarm

High Alarm

High Alarm

High Alarm

The status for "High Alarm" and its associated time stamp.

Settings of 5 subelements see in the following part.

-

HI_HI_ALM

HI_HI_ALM

HI_HI_ALM

HI_HI_ALM

High High Alarm

High High Alarm

High High Alarm

High High Alarm

Mix

The status for High High Alarm and its associated time stamp.

Settings of 5 subelements see in the following part.

-

Settings of 5 subelements for previous 2 parameters High Alarm and High High Alarm:

UNACKNOWLEDGED

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

ALARM_STATE

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

SUB_CODE

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

Other

Setting:

Other / Block Configuration / Link Configuration / Simulation

Active / Local Override / Device Fault State / Device

Maintenance / Input Failure / Output Failure / Memory

Failure / Lost Static Data / Lost NV Data / Readback Check /

Maintenance Needed / Power Up / Out Of Service

VALUE

Float Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

HI_HI_LIM

HI_HI_LIM

HI_HI_LIM

HI_HI_LIM

High High Limit

High High Limit

High High Limit

High High Limit

R/W

The setting for "High High Alarm" in engineering units.

NaN

Setting:

-3.39E38...+3.39E38 / -INF (-infinite) / + INF (+infinite)

HI_HI_PRI

HI_HI_PRI

HI_HI_PRI

HI_HI_PRI

High High Priority

High High Priority

High High Priority

High High Priority

R/W

Priority of the "High High Alarm".

0

Setting:

0...15

HI_LIM

HI_LIM

HI_LIM

HI_LIM

High Limit

High Limit

High Limit

High Limit

R/W

The setting for "High Alarm" in engineering units.

NaN

Setting:

-3.39E38...+3.39E38 / -INF (-infinite) / + INF (+infinite)