UNITS_INDEX

Units Index

R/W

Device Description units code index for the engineering unit

descriptor for the associated block value.

°

C

Setting:

K; °C; °F; °R

DECIMAL

Decimal

R

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

2

CALIBRATION_C1_1

CALIBRATION_C1_1

CALIBRATION_C1_1

CALIBRATION_C1_1

calibration

calibration

calibration

calibration

R/W

Calibration (Fct. C1.1)

-

Zero_Point

zero calibration

R

Zero calibration (manual setting) (Fct. C1.1.1)

0.0

Setting:

-1.0…+1.0

Size_Entry

size entry

R

Size entry (Fct. D2.4)

2

Setting:

1: value in [m] / 2: table [mm & inch]

Sensor_Size_Tab

size

R/W

Size (Fct. C1.1.2)

2000

Setting:

DN2.5…3000 [mm] 1/10"…120"

GKL_Value

GKL

R/W

GKL (Fct. C1.1.5)

10.0

Setting:

0.5…20.0

Coil_Resist_Rsp

coil resistance Rsp

R/W

Coil resistance Rsp (Fct. C1.1.7)

60.0

Setting:

10.0…220.0

Coil_Temp_Calc

calib. coil temp.

R/W

Calibration coil temperature (Fct. C1.1.8)

293.15

Setting:

233.15…473.15

Density_Fact

density

R/W

Density (Fct. C1.1.9)

1000.0

Setting:

100.0…5000.0

EF_Electr_Fact

EF electr.factor

R/W

Calibrate electrode factor EF (Fct. C1.1.11)

0.003

Setting:

0.0001...0.030

Field_Frequency

field frequency

R/W

Field frequency (Fct. C1.1.13)

7

Setting:

5: 1/2*line frequency / 6: 1/4*line frequency / 7: 1/6*line

frequency / 8: 1/8*line frequency / 9: 1/12*line frequency / 10:

1/18*line frequency / 11: 1/36*line frequency / 12: 1/50*line

frequency

FILTER_C1_2

FILTER_C1_2

FILTER_C1_2

FILTER_C1_2

filter

filter

filter

filter

Filter (Fct. C1.2)

-

Limitation_Low

limitation min

R/W

Limitation min process input (Fct. C1.2.1)

-12.0

Setting:

-100.000…-0.001

Limitation_High

limitation max

R/W

Limitation max process input (Fct. C1.2.1)

12.0

Setting:

0.001…100.000

Flow_Direction

flow direction

R/W

Flow direction (Fct. C1.2.2)

0

Setting:

0: normal / 1: reverse

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value