Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual
Page 19
OPERATION
4
19
IFC 100
www.krohne.com
02/2012 - 4001702901 - AD IFC 100 FF R01 en
DIAGNOSIS_BLK
DIAGNOSIS_BLK
DIAGNOSIS_BLK
DIAGNOSIS_BLK
Diagnosis Block
Diagnosis Block
Diagnosis Block
Diagnosis Block
Detailed diagnosis of the blocks.
-
RB_DIAG
RB
R
Reason for bits set at BLK_ERR and other diagnosis.
Current diagnosis
Setting:
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / Operating System / new : ID , DEV_TYPE , SNR /
no GDC Communication / Startup GDC, data invalid / Startup
Sensor, data valid / C-Number doesn't match to FF Software /
Hardware changed, Craw != C detected / Data Base doesn't
match to FF Software / MODE_BLK.PERMITTED doesn't
include Auto / MODE_BLK.TARGET is set OOS / GDC bold F
message / GDC F message / Write from GDC to RB/TB doesn't
work / GDC Mfr unknown / GDC serial number / Boardinfo
incomplete or corrupt / action : write from GDC to RB/TB /
GDC W : no, M : no / GDC W : no, M : some /
GDC W : some, M : no / GDC W : no, M : all /
GDC W : all, M : no / GDC W : some, M : some /
GDC W : some, M : all / GDC W : all, M : some /
GDC Communication few loss / RS_STATE is not On-Line /
simulation active / SET_FSTATE was set / unknown reason /
ok
TB_DIAG
TB
R
Reason for bits at BLK-ERR and other diagnosis.
Current diagnosis
Setting:
Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory
failure / no GDC Communication / Startup GDC, data invalid /
Startup Sensor, data valid / Data Base doesn't match to FF
Software / MODE_BLK.PERMITTED doesn't include Auto /
MODE_BLK.TARGET is set OOS / GDC bold F message / GDC F
message / Write from GDC to RB/TB doesn't work / Sensor
serial number / Sensor calibration date / GDC unit not
convertible to TB.prim_val / prim_val is outside range /
action : write from GDC to RB/TB / GDC Communication few
loss / No unit of GDC / GDC unit can't be converted to
TB.prim_range / a GDC value was not received / a GDC short
status is fatal or warn2 / PRIMARY_VALUE_1.status is
Uncertain / unknown reason / ok
AI1/2/3_DIAG
AI1/2/3
R
Reason for Out.status not good, bits at BLK-ERR and other
diagnosis.
Current diagnosis
Setting:
Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution too large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
CHANNEL is uninitialized / UNIT of CHANNEL selected
TB.prim_val not convertible to XD UNIT / XD_SCALE :
difference between EU_100 and EU_0 is too less / OUT_SCALE
: difference between EU_100 and EU_0 is too less / L_TYPE is
uninitialized / L_TYPE is direct , XD_SCALE is not equal
OUT_SCALE / IO-OPTS no unit conversion, XD UNIT doesnt´t
match to UNIT of TB.prim_val / SIMULATE_STATUS is not
Good, Simulation is active / SIMULATE_STATUS limitted,
STATUS_OPTS is set, Simulation active / Simulation is active /
Transducer Block MODE_BLK.ACTUAL is OOS / CHANNEL
selected TB.prim_val.status is Bad / TB.prim_val.status is
limitted, STATUS_OPTS is set / CHANNEL selected
TB.prim_val.status is Uncertain / OUT.value exceeds
OUT_SCALE / unknown reason / ok