DIAGNOSIS_BLK

DIAGNOSIS_BLK

DIAGNOSIS_BLK

DIAGNOSIS_BLK

Diagnosis Block

Diagnosis Block

Diagnosis Block

Diagnosis Block

Detailed diagnosis of the blocks.

-

RB_DIAG

RB

R

Reason for bits set at BLK_ERR and other diagnosis.

Current diagnosis

Setting:

Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory

failure / Operating System / new : ID , DEV_TYPE , SNR /

no GDC Communication / Startup GDC, data invalid / Startup

Sensor, data valid / C-Number doesn't match to FF Software /

Hardware changed, Craw != C detected / Data Base doesn't

match to FF Software / MODE_BLK.PERMITTED doesn't

include Auto / MODE_BLK.TARGET is set OOS / GDC bold F

message / GDC F message / Write from GDC to RB/TB doesn't

work / GDC Mfr unknown / GDC serial number / Boardinfo

incomplete or corrupt / action : write from GDC to RB/TB /

GDC W : no, M : no / GDC W : no, M : some /

GDC W : some, M : no / GDC W : no, M : all /

GDC W : all, M : no / GDC W : some, M : some /

GDC W : some, M : all / GDC W : all, M : some /

GDC Communication few loss / RS_STATE is not On-Line /

simulation active / SET_FSTATE was set / unknown reason /

ok

TB_DIAG

TB

R

Reason for bits at BLK-ERR and other diagnosis.

Current diagnosis

Setting:

Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory

failure / no GDC Communication / Startup GDC, data invalid /

Startup Sensor, data valid / Data Base doesn't match to FF

Software / MODE_BLK.PERMITTED doesn't include Auto /

MODE_BLK.TARGET is set OOS / GDC bold F message / GDC F

message / Write from GDC to RB/TB doesn't work / Sensor

serial number / Sensor calibration date / GDC unit not

convertible to TB.prim_val / prim_val is outside range /

action : write from GDC to RB/TB / GDC Communication few

loss / No unit of GDC / GDC unit can't be converted to

TB.prim_range / a GDC value was not received / a GDC short

status is fatal or warn2 / PRIMARY_VALUE_1.status is

Uncertain / unknown reason / ok

AI1/2/3_DIAG

AI1/2/3

R

Reason for Out.status not good, bits at BLK-ERR and other

diagnosis.

Current diagnosis

Setting:

Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory

failure / no schedule / period of execution / period of

execution too large / MODE_BLK.PERMITTED doesn't include

Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is

set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /

CHANNEL is uninitialized / UNIT of CHANNEL selected

TB.prim_val not convertible to XD UNIT / XD_SCALE :

difference between EU_100 and EU_0 is too less / OUT_SCALE

: difference between EU_100 and EU_0 is too less / L_TYPE is

uninitialized / L_TYPE is direct , XD_SCALE is not equal

OUT_SCALE / IO-OPTS no unit conversion, XD UNIT doesnt´t

match to UNIT of TB.prim_val / SIMULATE_STATUS is not

Good, Simulation is active / SIMULATE_STATUS limitted,

STATUS_OPTS is set, Simulation active / Simulation is active /

Transducer Block MODE_BLK.ACTUAL is OOS / CHANNEL

selected TB.prim_val.status is Bad / TB.prim_val.status is

limitted, STATUS_OPTS is set / CHANNEL selected

TB.prim_val.status is Uncertain / OUT.value exceeds

OUT_SCALE / unknown reason / ok