Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual
Page 31
OPERATION
4
31
IFC 100
www.krohne.com
02/2012 - 4001702901 - AD IFC 100 FF R01 en
Diagnosis_Value
diagnosis value
R/W
diagnosis value (Fct. C1.3.17)
8
Setting:
25: off / 31: electrode noise / 8: terminal 2 DC /
9: terminal 3 DC
SENSOR_CAL_DATE
SENSOR_CAL_DATE
SENSOR_CAL_DATE
SENSOR_CAL_DATE
Sensor Calibration
Sensor Calibration
Sensor Calibration
Sensor Calibration
Date
Date
Date
Date
R
The date of the last measuring sensor calibration.
-
SENSOR_SN
SENSOR_SN
SENSOR_SN
SENSOR_SN
Sensor Serial Number
Sensor Serial Number
Sensor Serial Number
Sensor Serial Number
R
The serial number of the measuring sensor.
-
SENSOR_TYPE
SENSOR_TYPE
SENSOR_TYPE
SENSOR_TYPE
Sensor Type
Sensor Type
Sensor Type
Sensor Type
R
The type of measuring sensor.
102
Setting:
102 (= Electromagnetic)
TRANSDUCER_
TRANSDUCER_
TRANSDUCER_
TRANSDUCER_
DIRECTORY
DIRECTORY
DIRECTORY
DIRECTORY
Transducer Directory
Transducer Directory
Transducer Directory
Transducer Directory
R
A directory that specifies the number and starting indices of
the transducers in the Transducer Block.
0
Setting:
0...65535
TRANSDUCER_
TRANSDUCER_
TRANSDUCER_
TRANSDUCER_
TYPE
TYPE
TYPE
TYPE
Transducer Type
Transducer Type
Transducer Type
Transducer Type
R
Identifies the transducer type. This is included in all the 4
views as per definition given in the standard pressure
transducer block given by FF.
Other
XD_ERROR
XD_ERROR
XD_ERROR
XD_ERROR
Transducer Error
Transducer Error
Transducer Error
Transducer Error
R
One of the transducer error codes defined in the FF
Transducer Specifications in "Block Alarm Subcodes".
0
Setting:
16: Unspecified error (An error has occurred that was not
identified.)
17: General error (An error has occurred that could not be
classified as one of the errors below.)
18: Calibration error (An error occurred during calibration of
the device or a calibration error has been detected during
operation of the device.)
19: Configuration error (An error occurred during
configuration of the device or a configuration error has been
detected during operation of the device.)
20: Electronics Failure (An electronic component has failed.)
21: Mechanical Failure (An mechanical component has failed.)
22: I/O Failure (An I/O failure has occurred.)
23: Data Integrity Error (Indicates that data stored within the
system may not longer be valid due to NVM checksum failure.
Data verify after write failure, etc.)
24: Software Error (The software has detected an error. This
could be caused by an improper interrupt service routine, an
arithmetic overflow, a watchdog timer, etc.)
25: Algorithm Error (The algorithm used in the Transducer
Block produced an error. This could be due to an overflow,
data reasonableness failure, etc.)
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value