Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual
Page 30
4
OPERATION
30
IFC 100
www.krohne.com
02/2012 - 4001702901 - AD IFC 100 FF R01 en
Time_Const
time constant
R/W
Time constant process input (Fct. C1.2.3)
0.75
Pulse_Filter
pulse filter
R/W
Pulse filter (Fct. C1.2.4)
0
Setting:
0: off / 1: on / 2: automatic
Pulse_Width
pulse width
R/W
Pulse width A (Fct. C1.2.5)
0.2
Setting:
0.001…20.0
Pulse_Limitation
pulse limitation
R/W
Pulse limitation (Fct. C1.2.6)
0.05
Setting:
0.01…100.0
Noise_Filter
noise filter
R/W
Noise filter (Fct. C1.2.7)
0
Setting:
0: off / 1: on
Noise_Level
noise level
R/W
Noise level (Fct. C1.2.8)
0.1
Setting:
0.01…10.00
Noise_Suppression
noise suppression
R/W
Noise suppression (Fct. C1.2.8)
2.0
Setting:
1.0…10.00
Low_Flow_Cutoff
lfc threshold
R/W
Low flow cutoff threshold process input (Fct. C1.2.10)
0.02
Setting:
0.0…10.00
Hysterisis
lfc hysteresis
R/W
Low flow cutoff hysteresis process input (Fct. C1.2.10)
0.0
Setting:
0.0…10.0
Conductivity
conductivity
R/W
Time constant conductivity (Fct. C1.2.11)
1.0
Setting:
0.1…100.0
SELF_TEST_C1_3
SELF_TEST_C1_3
SELF_TEST_C1_3
SELF_TEST_C1_3
self test
self test
self test
self test
R/W
Self test (Fct. C1.3)
-
Empty_Pipe
empty pipe detect
R/W
empty pipe detect (Fct. C1.3.1)
0
Setting:
0: off / 1: conductivity / 2: cond.+empty pipe (S) /
3: cond.+empty pipe (F) / 4: cond.+empty pipe (I)
Limit_Empty_Pipe
limit empty pipe
R/W
limit empty pipe (Fct. C1.3.2)
0.006
Setting:
0.0…0.9999
Electrode_Noise
electrode noise
R/W
electrode noise (Fct. C1.3.13)
0
Setting:
0: off / 1: on
LimitElectrNoise
limit electr.noise
R/W
limit electrode noise (Fct. C1.3.14)
0.1
Setting:
0.0...12.0
Settling_Field
settling of field
R/W
settling of field (Fct. C1.3.16)
0
Setting:
0: off / 1: on
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value