Operation – KROHNE IFC 100 Converter FOUNDATION FIELDBUS User Manual

Page 44

background image

4

OPERATION

44

IFC 100

www.krohne.com

02/2012 - 4001702901 - AD IFC 100 FF R01 en

Units Index

R/W

Setting:

All units are possible.

-

Decimal Point

R/W

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

0

OUT_TRIP

OUT_TRIP

OUT_TRIP

OUT_TRIP

Output Trip

Output Trip

Output Trip

Output Trip

R/W

The first discrete output.

-

Status

R/W

Setting:

Good Non Cascade / Good Cascade / Uncertain / Bad Not

Connected / Bad

Bad Not Connected

Value

R/W

Setting:

0: Off / 1: On

Off

OUTAGE_LIM

OUTAGE_LIM

OUTAGE_LIM

OUTAGE_LIM

Outage Limit

Outage Limit

Outage Limit

Outage Limit

R/W

The maximum tolerated duration for power failure.

0

Setting:

Positive or 0

PCT_INCL

PCT_INCL

PCT_INCL

PCT_INCL

Percentage

Percentage

Percentage

Percentage

Increment

Increment

Increment

Increment

Calculation

Calculation

Calculation

Calculation

R

Indicates the percentage of inputs with good status compared

to the ones with bad or uncertain and bad status.

0.0

PRE_TRIP

PRE_TRIP

PRE_TRIP

PRE_TRIP

Pre Trip

Pre Trip

Pre Trip

Pre Trip

R/W

Adjusts the amount of mass, volume or energy that should set

OUT_PTRIP when the integration reaches (TOTAL_SP -

PRE_TRIP) when counting up or PRE_TRIP when counting

down.

0

Setting:

Positive or 0

PULSE_VAL1

PULSE_VAL1

PULSE_VAL1

PULSE_VAL1

Pulse Value 1

Pulse Value 1

Pulse Value 1

Pulse Value 1

R/W

Determines the mass, volume or energy per pulse.

0.0

Setting:

Positive or 0

PULSE_VAL2

PULSE_VAL2

PULSE_VAL2

PULSE_VAL2

Pulse Value 2

Pulse Value 2

Pulse Value 2

Pulse Value 2

R/W

Determines the mass, volume or energy per pulse.

0.0

Setting:

Positive or 0

RESET_CONFIRM

RESET_CONFIRM

RESET_CONFIRM

RESET_CONFIRM

Reset Confirm

Reset Confirm

Reset Confirm

Reset Confirm

R/W

Momentary discrete value which can be written by a host to

enable further resets, if the option confirm reset in

INTEG_OPTS is chosen.

-

Status

R/W

Setting:

Good Non Cascade / Good Cascade / Uncertain / Bad Not

Connected / Bad / Bad No Comm with Last Useable Value

(LUV)

Bad Not Connected

Value

R/W

Setting:

0: Off / 1: On

Off

RESET_IN

RESET_IN

RESET_IN

RESET_IN

Reset Input

Reset Input

Reset Input

Reset Input

R/W

Reset the totalizers.

-

Status

R/W

Setting:

Good Non Cascade / Good Cascade / Uncertain / Bad Not

Connected / Bad / Bad No Comm with Last Useable Value

(LUV)

Bad Not Connected

Value

R/W

Setting:

0: Off / 1: On

Off

REV_FLOW1

REV_FLOW1

REV_FLOW1

REV_FLOW1

Reverse Flow 1

Reverse Flow 1

Reverse Flow 1

Reverse Flow 1

R/W

Indicates reverse flow when true.

-

Status

R/W

Setting:

Good Non Cascade / Good Cascade / Uncertain / Bad Not

Connected / Bad / Bad No Comm with Last Useable Value

(LUV)

Bad Not Connected

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value